OPERATION
CABLE SIZE:
When a long electric extension cord is used to connect an appliance or
tool to the generator, a certain amount of voltage drop or loss occurs in
the extension cord which reduces the effective voltage available for the
appliance or tool. The chart below has been prepared to illustrate the
approximate voltage loss when an extension cord of 300 feet (approx.
100 meters) is used to connect an appliance or tool to the generator.
Equipment damage can result from low voltage. Therefore, to prevent
excessive voltage drop between the generator and the equipment,
the cable should be of adequate gauge for the length used. The cable
selection chart gives the maximum cable lengths for various gauges of
wire which can adequately carry the loads shown.
CURRENT
LOAD IN WATTS
IN AMPS
120 VOLTS
2.5
300
5
600
7.5
900
10
1200
15
1800
20
2400
25
3000
30
3600
40
4800
Operator's Manual
Operating the Generator
240 VOLTS
#8 WIRE
600
1200
1800
2400
3600
4800
175
6000
150
7200
125
9600
90
MAXIMUM CABLE LENGTH (FEET)
#10 WIRE
#12 WIRE
1000
600
500
300
350
200
250
150
150
100
125
75
100
60
65
#14 WIRE
#16 WIRE
375
250
200
125
125
100
100
50
65
50
29