Electrical test data
• Software class
• Contamination class
• Rated surge voltage
• Temperature of ball impact test
The test for electromagnetic compatibility (interference
emission test) was performed at the rated voltage and rated
current.
Electrical installation
Electrical installation work must only be performed by a
qualified electrician. This work must be carried out in
accordance with the regulations to IEC 60364-7-701
(corresponding to VDE 0100 Part 701) as well as all
national and local regulations.
Only water-resistant round cables with max. outside diameter
of 6.0 to 8.5 mm may be used.
Installation
A vacant tube is required for the line between switched-mode
power supply and electronics.
Plaster and tile the wall, excluding the area of the structural
shell protection.
Operation,
Activating cleaning mode,
see page 3.
Flow volume setting,
see page 3.
Setting the programme, see page 4.
*F: Cleaning mode: The water flow can be
temporarily locked.
*G: Interval of automatic flushing, usage-
independent.
*H: Interval of automatic flushing, usage-
dependent.
*J: Pre-flush: flushing is initiated 2 sec. after
detection. WC: 3 l, Urinal: 1 - 2 l.
*K: Flush during continuous detection. WC:
every 60 min. (max. 3x), Urinal: every 2 min.
(max. 14x).
*L: Detection zone.
Fault / Cause / Remedy
Fault
LED in electronics flashing
continuously after
calibration
No flushing
3
2500 V
Cause
• Obstacle during calibration
• Servo motor defective
• No voltage (LED in electronics not
flashing)
• Electronics defective (LED not flashing or
permanently on)
• Servo motor defective
• Plug-in connector without contact
Intermediate flush
A
see page 4.
2
100 °C
Activating setting mode
Disconnect the power supply to the electronics and reconnect
after 10 s.
The indicator lamp in the sensor system illuminates in setting
mode when the detection zone of the fitting is reached by an
approaching user.
Setting mode is automatically terminated after 3 minutes.
Maintenance
• Shut off water supply
• Switch off voltage supply
• Inspect and clean all components and replace if
necessary.
Calibrating the servo motor
Caution: The servo motor must be calibrated outside the
cistern!
Care
For directions on the care of this fitting, please refer to the
accompanying Care Instructions.
Disposal note
This category of device does not belong in the domestic
waste, but must be disposed of separately in
accordance with the relevant national regulations.
Special accessories - The factory settings can be
changed and special functions can be activated,
deactivated and set using the infrared remote control
(Prod. no. 36 407). The current Technical Product
Information for the remote control can be downloaded
from www.grohe.com/tpi/remote-control.
Remedy
- Perform calibration again, ensuring there is no
obstacle in the adjustment range of the servo
motor
- Replace servo motor
- Switch on power supply or replace switched-
mode power supply
- Replace electronics
- Replace servo motor
- Attach plug-in connector
16
,