COMPUTER INTERFACE PORT

The computer interface port has the following technical characteristics and provides both the RS-232
interface and signals to contacts. The UPS can send power failure and battery failure signals and receive the
shutdown signal.
RS 232
S.D. =
Input shutdown signal: when the UPS is operating in Battery Mode, apply a positive signal
(+5÷15VDC) between this input (pin 3) and the common input (pin 5) for at least 20sec in order
to shutdown the unit.
B.W. = Contact closed when the UPS is operating in battery mode (max +30Vdc 10mA).
B.L. =
Contact closed when the UPS in operating off low batteries (max +30Vdc 10mA).
COM = Common
WARNING: only use the UPS monitoring system provided or systems recommended by the
manufacturer.
6
2
1
Sub D 9 female pin (computer interface connector)
9
8
7
3
4
5
- 32 -
TX pin 2
RX/S.D. pin 3
B.L. pin 8
B.W. pin 9
COM pin 5