Configuration - socomec COUNTIS Ci Instrucciones De Servicio

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 74

CONFIGURATION

NB:
Press the
button for a prolonged
period to scroll rapidly through the
configuration screens. Press for a
short period to scroll through each
screen one-by-one.
SOCOMEC - Ref. : 875 092A
KEYS
+
For active energy metering (EA), the following parameters are accessible:
Proceed as above for inputs 2, 3, 4, 5, 6 and 7.
For pulse metering (IMP), access input 2 directly and proceed as if for energy
configuration (see above).
For energy metering (EA) on at least the first 4 inputs, access the synchroni-
sation signal configuration.
Proceed as above for inputs 2, 3, 4, 5, 6 and 7.
INSTRUCTIONS
Press for 3 seconds to gain access-
code entry (CdE).
To enter code 168.
To accept code and access input
1 network configuration (pulse or EA).
To allocate input 1 to energy metering
(EA) or pulse metering (IMP).
Accept configuration.
To configure the kWh scales from the
following list: 0.01, 0.1, 1, 10, 100,
and 1000.
Accept scale configuration and pass
to input 2.
To configure internal synchronisation
signal (toP) from the following list:
8,10, 15, 20 and 30 minutes.
Accept signal and pass to reset
to zero (rSEt).
To select 'YES' and reset to zero
(or the contrary).
To accept zero reset and pass
to input 2.
21

Publicidad

Tabla de contenido
loading

Tabla de contenido