INSTALLATION
Position the unit in the open air out of direct sunlight.
It can be installed:
• with horizontal air discharge (standard version) for best protection (from snow or from objects falling from above) and easier maintenance; in this
configuration the unit must be protected from the wind which could interfere with the operation of the fan;
• with vertical air discharge; this configuration is recommended for installation in windy locations or where a horizontal air flow would be easily obstruc-
ted, available with optional leg kit.
Position the unit on a solid, level surface.
Use shims if necessary to ensure a level installation to within one degree. Fix the unit down using the appropriate bolt holes in the base (horizontal air
discharge) or in the bottoms of the legs (vertical air discharge)
If the unit is installed in places particularly subject to critical conditions such as:
- snowfall,
- sand storms,
- dense vegetation with danger of falling leaves,
- other critical conditions
the condenser must be covered over, leaving the recom-
mended working spaces (see paragraph: WORKING
SPACE) to maintain a correct airflow, correct unit heat
exchange and correct operation of the unit in general.
OK
EARTH
Earthing/grounding is compulsory by law. The instal-
ler must connect the earth wire, already connected to
earth/ground electrodes, to a point on the appliance
(earth/ground metric screw)
For BRC/BRE: in the low temperature, "LT" , versions, a check valve must be installed on the condenser outlet
Place the external condenser BRC/BRE with gas inlet from the top and the liquid output from the bottom. (See above picture)
24
BRC / BRE / BDC Instruction manual