MESSAGES
Pd
Pump down malfunction error (Shutdown)
LP
Pump down malfunction error (Start-up)
Probe 1/2/3 failure (Open circuit, crossed circuit or temperature outside the limits of the probe)
E1/E2/E3
(Equivalent limits in °F)
Ad0
Open door alarm. Only if the door stays open for a greater time than is indicated in parameter A12
Maximum temperature alarm in control probe. The temperature value programmed in A1 has been
AK
reached
Minimum temperature alarm in control probe. The temperature value programmed in A2 has been
AL
reached
AE
External alarm activated (by digital input)
Severe external alarm activated (by digital input)
AES
Adt
Defrost alarm concluded due to time-out. The time established in d1 has been exceeded
HACCP alarm. The temperature has reached the value of parameter h1 during a longer period than has
KCP
been established in h2
HACCP alarm due to a fault in the electric supply. The temperature established in h1 has been reached
HCP +
following a fault in the electric supply
PF
Indicates that a defrost is being performed
DEF
PAS
Access code (Password) request. See parameters b10 and PAS
S1 -
Shown sequentially with the temperature: The controller is in demo mode, the configuration has
not been made.
S2
A: Activates the acoustic alarm
R: Activates the alarm relay
18