Real time clock
It has a real time clock with date, hours and minutes indication, to make identifi-
cation of tests recorded in paper or in memory easier.
Test number
Tests are automatically numbered by the megohmmeter to make their identifica-
tion easier. The test number is printed at the beginning of each test and it is
stored in memory.
Model and serial number
At the beginning of each test, the equipment model as well as its serial number
are registered, making it possible to relate the obtained results with their re-
spective equipment Calibration Certificate.
Tests definition
The MD-5060x megohmmeter model is an extremely versatile, which al-
lows to carry out several kinds of insulation tests automatically, recording
all the results in its internal memory or printing them. That's why it is neces-
sary to define the tests properly, selecting its parameters before starting the
test:
•
Test voltage.
•
Equipment operation mode.
•
Minimum resistance limit, for the "Pass-fail test".
These three parameters shall be defined before starting the test. The test
voltage is the only parameter that can be modified during the test. The
*,.0 keys makes it possible to enter the different equipment program-
ming modes. The 7 (decrease) and 8 (increase) keys select the value.
The functions of the *,.0 keys are mutually exclusive. Selecting one of
these keys implies releasing any other selected key. The * and , keys
select the test voltage programming mode in 500 V or 100 V steps. When
one of these keys is on, the Decrease / Increase keys adjust the test volt-
age. Whenever the equipment is on, the ±500 voltage adjustment function
is on.
11