Check mode
To playback the recorded messages:
1.
Press the push button (Figure 6, item 4) for less than one
second.
Note:
If it is pressed for more than 1 second, you go back
into programming mode.
2.
Listen to the messages that you have been recorded.
Note:
At the end of either Record mode or Check mode,
there will be 7 beeps to indicate that the module is now
available for event reporting.
Programming the Advisor Advanced
Refer to the Advisor Advanced programming manual.
Programming the Advisor Master
After recording the messages, program the Advisor Master by
selecting the Voice protocol for 1 to 4 Central Stations (CS).
Program the voice protocol in Communications Options menu
19/9 for CS 1 to 4 with format No. 14 without Acknowledge:
Voice Reporting – No Acknowledge
Format No: 14
Set Suppress FTC for voice reporting option to YES.
YES–Suppress FTC for voice reporting
*-Change 0-Skip
Map the recording voice message to one of the reporting
codes via menu 19/52. Refer to Table 3 below.
Burglar Alarm – Voice Message 0
Msg No:
Voice message programming table
Voice messages can be programmed to report on the
occurrence of specific reporting codes. More than 1 reporting
code may have the same voice message programmed.
Reporting codes 1 to 11 are general alarms, while reporting
codes 12 to 21 are zone specific, that is, you can program the
reporting codes to specific zones. The range is from 1 to 14.
Table 3: Reporting codes
#
Reporting code
1.
Burglar Alarm
2.
Tamper Alarm
3.
Hold-up Alarm
4.
Panic Alarm
5.
Fire Alarm
6.
Medical Alarm
7.
Technical Alarm
8.
Mains Fail
9.
DGP Offline
10.
Area Disarmed
4 / 32
1st ATS7200E
2nd ATS7200E
installed
installed
Message no.
Message no.
1–6
1–14
1–6
1–14
1–6
1–14
1–6
1–14
1–6
1–14
1–6
1–14
1–6
1–14
1–6
1–14
1–6
1–14
1–6
1–14
#
Reporting code
11.
Area Armed
12.
130 BA Burglary
13.
131 BA Perimeter
14.
132 BA Interior
15.
133 BA 24 Hour
16.
134 BA Entry/Exit
17.
135 BA Day/Night
18.
136 BA Outdoor
19.
137 BA Tamper
20.
138 BA Near Alarm
21.
140 UA General Alarm
Default message number 0 = No message.
Reporting code 12 (130, BA Burglary) and reporting code 1 (Burglar
Alarm) are the same events. If reporting code 12 (130, Burglary) is
programmed with an alarm message, then this will override reporting
code 1 (Burglar Alarm).
Specifications
Power supply
Supply current
Recording capacity
Recording bandwidth
Dimensions
Weight
Temperature
Non-volatile memory
Automatic gain control during recording
Acknowledge by DTMF code
Regulatory information
Manufacturer
PLACED ON THE MARKET BY:
Carrier Fire & Security Americas Corporation Inc.
13995 Pasteur Blvd
Palm Beach Gardens, FL 33418, USA
AUTHORIZED EU REPRESENTATIVE:
Carrier Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
Product warnings
THESE PRODUCTS ARE INTENDED FOR SALE
and disclaimers
TO AND INSTALLATION BY QUALIFIED
PROFESSIONALS. CARRIER FIRE &
SECURITY CANNOT PROVIDE ANY
ASSURANCE THAT ANY PERSON OR ENTITY
BUYING ITS PRODUCTS, INCLUDING ANY
"AUTHORIZED DEALER" OR "AUTHORIZED
RESELLER", IS PROPERLY TRAINED OR
EXPERIENCED TO CORRECTLY INSTALL FIRE
AND SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers and
product safety information, please check
https://firesecurityproducts.com/policy/product-
warning/ or scan the QR code.
P/N 466-2983 (ML) • REV B • ISS 10DEC20
1st ATS7200E
2nd ATS7200E
installed
installed
Message no.
Message no.
1–6
1–14
1–6
1–14
1–6
1–14
1–6
1–14
1–6
1–14
1–6
1–14
1–6
1–14
1–6
1–14
1–6
1–14
1–6
1–14
1–6
1–14
12 V via ribbon cable
from control panel
50 mA
8 messages
(total recording time 40 s)
3 kHZ
80 x 50 x 20 mm
123 g
+10 to 50°C
Yes