Detail 2
Indoor Unit "A"
Indoor Unit "B"
CAB-SERV
CAB-SERV
Ground line Remote Controller (Do not connect)
CN-RMT
A1 A2 A3 A4 B1 B2 B3 B4
DIP-SW
PAW-SERVER-PKEA-1
I1 I1 I2 I2 O1 O1 O2 O2 O3 O3 O4 O4
Remote Controller
Connect the Remote Controller to the CN-RMT plug on the top-left side of the
PAW-SERVER-PKEA-1.
The ground line of the Remote Controller cable has NO connection (you may also cut the wire).
Conect the 4 wires cable between
PAW-SERVER-PKEA-1
and the unit "A" and "B" paying attention to
the terminal labels:
A1 -> YELLOW wire of CAB-SERVER, indoor unit "A" (Ground);
A2 -> WHITE wire of CAB-SERVER, indoor unit "A" (+12 Vdc);
A3 -> GREEN wire of CAB-SERVER, indoor unit "A" (Tx signal);
A4 -> BROWN wire of CAB-SERVER, indoor unit "A" (Rx signal);
Shield (not connected to PAW-SERVER-PKEA-1) -> Green wire of CAB-SERVER
B1 -> YELLOW wire of CAB-SERVER, indoor unit "B" (Ground);
B2 -> WHITE wire of CAB-SERVER, indoor unit "B" (+12 Vdc);
B3 -> GREEN wire of CAB-SERVER, indoor unit "B" (Tx signal);
B4 -> BROWN wire of CAB-SERVER, indoor unit "B" (Rx signal);
Shield (not connected to PAW-SERVER-PKEA-1) -> Green wire of CAB-SERVER
In the lower part of the PAW-SERVER-PKEA-1 you can find 2 INPUT and 4 OUTPUT Dry Contacts.
OUTPUT Dry Contacts can handle max. 48 Volt - 3 Ampere.