The air-fume end piece and ducts must be free of obstructions and leaks
The burner and exchanger must be clean and free of deposits. For possible clean-
ing do not use chemical products or wire brushes.
The gas and water systems must be airtight.
The water pressure in the cold water system must be approx. 1 bar; otherwise, bring
it to that value.
The circulating pump must not be blocked.
The expansion tank must be filled.
Check the magnesium anode and replace it if necessary.
A
The boiler casing, control panel and aesthetic parts can be cleaned with a soft
and damp cloth, if necessary soaked in soapy water. Do not use any abrasive
detergents and solvents.
Boiler cleaning
1.
Disconnect the power supply to the boiler.
2.
Remove the front top and bottom panel.
3.
Open the door by undoing the knobs.
4.
Clean the inside of the boiler and the entire path of exhaust fumes, using a tube
brush or compressed air.
5.
Then close the door, securing it with the knob.
To clean the burner, refer to the Manufacturer's instructions.
4.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault,
the display will flash together with the fault symbol (detail 22 - fig. 1) indicating the fault
code.
There are faults that cause permanent shutdown (marked with the letter "A"): to restore
operation just press the RESET button (detail 8 - fig. 1) for 1 second or RESET on the
optional remote timer control if installed; if the boiler fails to restart, it is necessary to elim-
inate the fault indicated by the operation LEDs.
Faults marked with the letter "F" cause temporary shutdowns that are automatically reset
as soon as the value returns within the boiler's normal working range.
Table of faults
Table. 2 - List of faults
Fault
Fault
code
A01
Burner shutdown
Flame present signal
A02
with burner off
Overtemperature pro-
A03
tection activation
F07
Preheater fault
F10
Delivery sensor 1 fault
F11
DHW sensor fault
F14
Delivery sensor 2 fault
Supply voltage under
F34
170V.
Faulty mains fre-
F35
quency
Incorrect system water
F37
pressure
F39
External probe fault
Incorrect system water
F40
pressure
A41
Sensor positioning
F42
Heating sensor fault
System water pressure
F47
sensor fault
cod. 3540Z340 - 03/2011 (Rev. 00)
Possible cause
Cure
Pump blocked
Replace
Faulty electric motor
Replace
Faulty oil valve
Replace
No fuel in tank, or water on bottom
Refill with fuel or suck the water
Oil line supply valves closed
Open
Dirty filters (line-pump-nozzle)
Clean
Pump unprimed
Prime and find the cause of
unpriming
Ignition electrodes dirty or not properly
Adjust or clean them
adjusted
Nozzle clogged, dirty or deformed
Replace
Unsuitable head and shutter adjustments Adjust
Electrodes faulty or earthed
Replace
Faulty ignition transformer
Replace
Electrodes faulty or earthed
Replace
Electrode wires deformed by high tem-
Replace and protect
perature
Faulty valve or transformer electrical con-
Check
nections
Broken pump-motor joint
Replace
Pump inlet connected to return pipe
Correct the connection
Faulty photoresistance
Replace
Dirty photoresistance
Clean the photoresistance
Photoresistance short circuit
Replace photoresistance
Extraneous light strikes the photoresist-
Eliminate light source
ance
Check correct positioning and
Heating sensor damaged
operation of the heating sensor
No water circulation in the system
Check the circulating pump
Air in the system
Vent the system
Preheater fault
Check the preheater
Wiring disconnected
Check the wiring
Sensor damaged
Check the wiring or replace the
Wiring shorted
sensor
Wiring disconnected
Sensor damaged
Check the wiring or replace the
Wiring shorted
sensor
Wiring disconnected
Sensor damaged
Check the wiring or replace the
Wiring shorted
sensor
Wiring disconnected
Electric mains trouble
Check the electrical system
Electric mains trouble
Check the electrical system
Pressure too low
Fill the system
Sensor damaged
Check the sensor
Check the wiring or replace the
Probe damaged or wiring shorted
sensor
Probe disconnected after activating the
Reconnect the external probe or
sliding temperature
disable the sliding temperature
Check the system
Pressure too high
Check the safety valve
Check the expansion tank
Check correct positioning and
Delivery sensor not inserted in boiler shell
operation of the heating sensor
Sensor damaged
Replace the sensor
Wiring disconnected
Check the wiring
EN
15