Installation Guide
2
2 × 2m × 1 . 5 × 5
× 0 . 01786 Ω × m
A =
2
2 . 5 VA × mm
1.9 Four-wire System
All descriptions in the previous sections and following illustrations are targeting 3-wire systems. The filter can also operate in 4-wire
systems. Additional to the steps already described and illustrated, the following must be done:
rd
A 3
CT must be installed on phase 2/phase B.
The Neutral wire must be connected to the mains terminal.
In the PC tool for the filter, adjust the grid topology to 3P4W.
FILTER MALFUNCTION
Connecting the neutral wire in 3-wire applications will cause the filter to work improperly.
-
Do not connect the neutral wire in 3-wire applications.
1.10 Power Losses and Efficiency
For power loss data including part load losses, see https://ecosmart.mydrive.danfoss.com.
1.11 Cable and Fuse Specifications
The filter is protected internally with semiconductor fuses. Branch protection is subject to local installation conditions and regula-
tions, and thus no recommendations can be made. To support selection of suitable branch protection, the internal fuses of the filter
are specified in the following table.
L1/L2/L3 cross-section
Maximum stripping
Torque
Material
Temperature rating
PE cross-section
Maximum stripping
Cable lug
Torque
Material
Temperature rating
CT cables cross-section
Torque
Control cables cross-section
Danfoss A/S © 2023.01
2
= 1 . 07 mm
N O T I C E
35 A module
2
Rigid: 2.5–35 mm
(2 AWG)
2
Flexible: 2.5–25 mm
(14–4 AWG)
Flexible with ferrule: 2.5–25 mm
18 mm (0.7 in)
2.5–3.0 Nm (22.12–26.5 in-lb)
Copper
70 °C (158 °F)
2
16 mm
(6 AWG)
18 mm (0.7 in)
O-type 5–6 mm
2.5–3.0 Nm (22.12–26.5 in-lb)
Copper
70 °C (158 °F)
2
2.5 mm
(14 AWG)
0.8 Nm (7.1 in-lb)
2
1 mm
(17 AWG)
55 A module
Rigid: 2.5–35 mm
Flexible: 2.5–25 mm
2
(14–4 AWG)
Flexible with ferrule: 2.5–25 mm
18 mm (0.7 in)
2.5–3.0 Nm (22.12–26.5 in-lb)
Copper
70 °C (158 °F)
2
16 mm
(6 AWG)
18 mm (0.7 in)
O-type 5–6 mm
2.5–3.0 Nm (22.12–26.5 in-lb)
Copper
70 °C (158 °F)
2
2.5 mm
(14 AWG)
0.8 Nm (7.1 in-lb)
2
1 mm
(17 AWG)
AN43084697267901-000101 / 130R1374 | 9
Installation
2
(2 AWG)
2
(14–4 AWG)
2
(14–4 AWG)

Publicidad

loading

Este manual también es adecuado para:

137g3607137g3610