Refrigerant piping work
(b) SET-FREE MINI FS(V)NME / FSXNME Series
model
connectable indoor unit
(recommended number) *1)
RAS-4FS(V)NME
RAS-5FS(V)NME
RAS-6FS(V)NME
RAS-8FSXNME
RAS-10FSXNME
RAS-12FSXNME
(c) UTOPIA IVX Series
model
connectable indoor unit
(recommended number) *1)
RAS-2HVNP1
RAS-2.5HVNP1
RAS-3HVNC1
RAS-4H(V)NC1E
RAS-5H(V)NC1E
RAS-6H(V)NC1E
RAS-8HNCE
RAS-10HNCE
RAS-12HNC
*1) There are some notices for the connectable number of indoor units depending on the connected indoor unit model, the indoor
unit capacity, environment and installation place. Refer to the Technical Catalog of outdoor unit for the selection.
*2) It is within the connected number of indoor units.
*3) It is the total piping length between each expansion valve kit and the indoor unit.
*4) Refer to the Technical Catalog of outdoor unit for the calculation of additional refrigerant charge quantity.
8
max. number of
connectable expansion
13 (6) Units
16 (7) Units
18 (8) Units
26 (8) Units
32 (10) Units
39 (10) Units
max. number of
connectable expansion
2 (1) Units
2 (1) Units
2 (1) Units
4 (2) Units
4 (2) Units
4 (2) Units
4 Units
4 Units
4 Units
PMML0268A rev.4 - 02/2020 - P5416576
restrictions
max. number of
total piping length between
each expansion valve kit and
valve kit *2)
No restriction
restrictions
max. number of
total piping length between
each expansion valve kit and
valve kit *2)
2 Kits
2 Kits
2 Kits
4 Kits
4 Kits
4 Kits
4 Kits
4 Kits
4 Kits
indoor unit (m) *3)
30
40
60
indoor unit (m) *3)
No restriction
max. additional
refrigerant charge
quantity (kg) *4)
9.3
8.9
8.9
26.1
26.1
26.1
max. additional
refrigerant charge
quantity (kg) *4)
1.5
1.2
1.2
1.6
2.7
2.7
10.3
12.1
12.1