OPERATION
Register
Address
1078
1077
1079
1078
1080
1079
1081
1080
1082
1081
1083
1082
1084
1083
1085
1084
1086
1085
1087
1086
1088
1087
1089
1088
1090
1089
1091
1090
?
N O T E
1 These numbers are expressed as a signed 16-bit value using 2-complement format for negative values.
2 Only for Heating and Cooling units.
3 This value is limited by the machine according to their rank.
12
PMML0359A rev.1 - 06/2015
Description
Operation State
Outdoor Ambient Tº
(Outdoor ambient temperature)
Water Inlet Tº
(Water Inlet unit temperature)
Water outlet Tº
(Water outlet unit temperature)
Hardware version
Software version
H-LINK communication alarm state
LCD Software number
PCB1 Software number
Hitachi Room Thermostat set temperature C1
Hitachi Room Thermostat set temperature C2
Hitachi Room Thermostat temperature C1
Hitachi Room Thermostat temperature C2
Status Eco offset
Value
0: OFF
1: Cool Demand –OFF (2)
2: Cool Thermo-OFF (2)
3: Cool Thermo-ON (2)
4: Heat Demand-OFF
5: Heat Thermo-OFF
6: Heat Thermo-ON
7: DHW-OFF
8: DHW-ON
9: SWP-OFF
10: SWP-ON
11: Alarm
-80~100 (1)(3)
-80~100 (1)(3)
-80~100 (1)(3)
0: No alarm
1: There is no communication with
RCS or Yutaki unit during more
than 180 seconds
2: Data initialization
50~350 (5,0~35,0)
50~350 (5,0~35,0)
0~1000 (0,0~100,0)
0~1000 (0,0~100,0)
1~10
Type
R
R
R
R
R
R
R
R
R
R
R
R
R
R