DESCRIPTION OF TERMINAL BOARD
Name
Function
V+ BUS
Power supply positive
V-
Power supply negative
A
RS-485 data bus - A
B
RS-485 data bus - B
I1
Input connection
V+ AUX
Auxiliary power supply positive
TC (OUT)
Programmable output connection
(OC output, MAX 100 mA)
ALARM
ADDRESSING THE DEVICE ON THE BUS
Like any other device connected to the RS-485 bus, VEDO5TPR /
VEDO5TPRW must respond to a single address that can be configured
from the display.
1. Access the settings menu via
2. Type in the installer code (default=001961) and confirm
3. Follow the path "Alarm options -> Configuration -> Device ID"
4. Type in the identification number of the device on the bus
SETTING THE SPEED
1. Access the settings menu via
2. Type in the installer code (default=001961) and confirm
3. Follow the path "Alarm options -> Configuration -> RS-485 bus speed"
4. Select the desired speed. It is important to make sure that the value
is the same as in the Safe Manager configuration software (default
38400)