RX Series
The following chart may be used to record the changes made to the factory settings.
Fn #
Group
Function Description
Motor Nameplate FLA
F001
FLA must be programmed for
relay to function.
Motor Nameplate
F002
Service Factor
F003
Overload Class During Start
F004
Overload Class During Run
F005
Overload Reset
F006
Voltage Input (nominal Line)
kV Voltage Input (nominal
F007
line, Medium Voltage)
F008
Line Frequency
F009
Acceleration Time
F010
Current Imbalance Trip %
F011
Current Imbalance Trip Delay
F012
Over Current Trip %
F013
Over Current Trip Delay
F014
Under Current %
F015
Under Current Trip Delay
F016
Stall Detection Trip Level
F017
Stall Detection Trip Delay
F018
Peak Current Trip %
F019
Peak Current Trip Delay
Ground Fault Current Trip
F020
Value
Ground Fault Current Trip
F021
Delay
F022
Voltage Imbalance Trip %
F023
Voltage Imbalance Trip Delay
F024
Over Voltage Trip %
F025
Over Voltage Trip Delay
F026
Under Voltage Trip on Start %
F027
UV Trip on Start Delay
F028
Under Voltage Trip on Run %
F029
UV Trip Delay during Run
- 84 - |
P a g e
Digital Solid State Protection Relay 5 - 2000A
Adjustment / Display Range
1 - 2000
1.00 - 1.30 SF
NEMA / UL Class 5 - 30
NEMA / UL Class 5 - 30
0 = Manual
1 = Auto
2 = Disabled Overload
200 – 660 volt
.60 – 15kV
50 or 60 Hz
0-300 seconds [0=Disabled]
0, 1 - 30% of FLA [0=Disabled]
1 - 20 seconds
0, 50 – 300% of FLA [0=Disabled]
1 - 20 seconds
0, 10 – 90% of FLA [0=Disabled]
1 - 60 seconds
0, 100 – 600% of FLA [0=Disabled]
1 - 10 seconds
0, 800 – 1400% [0=Disabled]
0, .01 - .5 seconds
0, 5 – 90% of CT Value
[0=Disabled]
1 – 60 seconds
0, 1 – 30% [0=Disabled]
1 – 20 seconds
0, 1 – 10% [0=Disabled]
1 – 20 seconds
0, 1 – 30% [0=Disabled]
1 – 180 seconds
0, 1 – 20% [0=Disabled]
1 – 20 seconds
Setting
Factory
Setting Setting
Increments
Setting
1 amp
0
0.05
1.0 SF
5
Class 10
5
Class 10
0
1
(Manual)
1
480
.01
4.16
-
60
1
0
1 (%)
0
1
2
(Second)
1 (%)
0
1
1
1 (%)
0
1
2
5 (%)
0
1
2
10 (%)
0 (%)
.01
.05
1 (%)
0
1
2
1 (%)
0
1
10
1 (%)
0
1
10
1 (%)
0
1
10
1 (%)
0
1
2