Configuration
Use DIP-switches to configure the power supply settings.
The switch 6 must be set in OFF position.
Switch 1 – audible trouble signaling: ON=enabled / OFF=disabled.
Switch 2 – battery test: ON=enabled / OFF=disabled.
Switch 3 – battery charging current: ON=3 A / OFF=1,5 A.
Switches 4 and 5 – AC power failure reporting delay: see table below.
Switch
4
5
Installation
Disconnect power before making any electrical connections.
Do not connect deeply discharged battery to the power supply (with voltage across unloaded
terminals below 11.5 V).
The used batteries must not be discarded, but should be disposed of in accordance with the
existing rules for environment protection.
The power supply should be permanently connected to the 230 VAC mains power. Make sure that the circuit
you select will always be alive and protected with a proper safety device.
As the emergency power source, use a 12 V sealed lead-acid battery or other 12 V battery with similar charging
characteristics. Match the battery capacity to the current consumption of the connected devices.
1. Remove the cover of power supply terminals (Fig. 5).
2. Use the DIP-switches (see Fig. 2) to configure the power supply.
3. If the connector for integration is to be used, connect to it the cable shown in Fig. 4 (Fig. 6).
4. If screw terminals are to be used for powering the devices, screw the wires to +12V and COM terminals.
5. Connect the battery wires (Fig. 3) to the connector on the electronics board (Fig. 7).
6. You can connect e.g. LEDs to the trouble signaling outputs or you can connect these outputs with control
panel zones.
7. Run the 230 VAC power cable through the cable gland (Fig. 8).
8. Screw the 230 VAC power wires: phase conductor to L terminal, neutral conductor to N terminal, and
protective conductor to PE terminal (Fig. 9).
9. Screw the element fastening the 230 VAC power cable (Fig. 10).
10. Replace the cover of power supply terminals (Fig. 11) and fasten it with a screw (Fig. 12).
11. Connect the battery: battery positive to red wire, negative – to black.
12. Turn on 230 VAC power. When the AC power is present, the power supply will signal it with a single beep
sound and the
If no LED is turned ON after powering on, this may suggest that the power output has been shorted to
common ground or there has been a voltage spike. The power supply enters the emergency mode then.
The declaration of conformity may be consulted at www.satel.pl/ce
3 s
OFF
OFF
LED turning ON.
APS-612
AC power failure reporting delay
60 s
ON
OFF
600 s
1800 s
OFF
ON
ON
ON
7