Descargar Imprimir esta página

mundoclima CL20019 Manual De Instalación Y Usuario página 40

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

For maintenance or scrap, please contact authorized service centers.
Maintenance by unqualified person may cause dangers.
Feed air conditioner with R290 refrigerant, and maintain the air conditioner in strictly
accordance with manufacturer's requirements. The chapter is mainly focused on special
maintenance requirements for appliance with R290 refrigerant. Ask repairer to read
after-sales technical service handbook for detailed information.
Qualification requirements of maintenance personnel
1.Special training additional to usual refrigerating equipment repair procedures is
required when equipment with flammable refrigerants is affected. In many countries,
this training is carried out by national training organisations that are accredited to
teach the relevant national competency standards that may be set in legislation. The
achieved competence should be documented by a certificate.
2.The maintenance and repair of the air conditioner must be conducted according to the
method recommended by the manufacturer. If other professionals are needed to help
maintain and repair the equipment, it should be conducted under the supervision of
individuals who have the qualification to repair AC equipped with flammable refrigerant.
Safety inspection must be taken before maintaining equipment with R290 refrigerant to
make sure the risk of fire is minimized. Check whether the place is well ventilated,
whether anti-static and fire prevention equipment is perfect.
While maintaining the refrigeration system, observe the following precautions before
operating the system.
1.General work area:
All maintenance staff and others working in the local area shall be instructed on the
nature of work being carried out. Work in confined spaces shall be avoided. The area
around the workspace shall be sectioned off. Ensure that the conditions within the area
have been made safe by control of flammable material.
2. Checking for presence of refrigerant:
The area shall be checked with an appropriate refrigerant detector prior to and during
work, to ensure the technician is aware of potentially toxic or flammable atmospheres.
Ensure that the leak detection equipment being used is suitable for use with all
applicable refrigerants, i.e.non-sparking, adequately sealed or intrinsically safe.
3.Presence of fire extinguisher:
If any hot work is to be conducted on the refrigeration equipment or any associated
parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry
powder or CO
fire extinguisher adjacent to the charging area.
2
Maintenance Notice
WARNING
Inspection of the Site
Operating Procedures
40

Publicidad

loading

Este manual también es adecuado para:

Mupo-09-h9