Descargar Imprimir esta página

Danfoss Supercal 5 Guia De Instalacion página 3

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 12
Supercal 5
9.4 All parameter displays are used to check the thermal energy meter or
to adjust the system. It must be checked that the regulated flow of the
system does not exceed the maximum permitted flow of the meter.
9.5 A commissioning protocol via the optical interface with the readout
software is recommended for a comprehensive functional check.
10 Temperature sensors mounting
10.1 Please select PT500 temperature sensors.
10.2 The temperature sensors are always paired. Only matched pairs are
supplied and may not be separated, extended or shortened, since
this affects the measuring accuracy.
10.3 When the cable length of temperature is less than 10m, please select
2-wire temperature sensor.
10.4 When the cable length of temperature is above 10m, please select
4-wire temperature sensor. Maximum is 20m.
10.5 Please use pocket with correct length. The measuring tip of the
temperature sensor part must be positioned in the center of the cross
section of the pipe.
11 Temperature sensors connections
4 wires sensor with
2 wires cable sensor
2 wires cable sensor
5/6 temperature high
5/6 temperature high
5/6 temperature high
7/8 temperature low
7/8 temperature low
6
7
8
5
5
6
w
r
w
r
w
r
12 Error messages
Temperature reference 1 A/D: A cable of the temperature sensor is
1
interrupted or not connected.
Temperature reference 2 A/D: A cable of the temperature sensor is
2
interrupted or not connected.
Temperature reference 1 A/D: A cable of the temperature sensor is
4
conected but its value can not be read out.
Temperature reference 2 A/D: A cable of the temperature sensor is
8
connected but its value can not be read out
16
Temperature sensor 1 < = min. Range error
32
Temperature sensor 1 > = max. Range error
64
Temperature sensor 2 < = min. Range error
128
Temperature sensor 2 > = maxß. Range error
512
The fow rate is higher than 1,5 qs
1024
The SC5 is open
2048
Power outage
M1 Power Supply / M1 Unsupported / Slot left error: Error in module 1:
4096
Details must be found into specifc module error
M2 Power Supply / M2 Unsupported / Slot right error: Error in module 2:
8192
Details must be found into specifc module error
Errors will be registered in the error register with its date and time (beginning)
and dura tion (in minutes).
AN41283838560601-010101
Seal
Pocket
4 wires sensor with
4 wires cable sensor
4 wires integrator
4 wires sensor with
2 wires integrator
1/5 + 2/6 temperature high
1/5 + 2/6 temperature high
2 wires integrator
3/7 + 4/8 temperature low
5/6 temperature high
7/8 temperature low
3/7 + 4/8 temperature low
7/8 temperature low
5
7
6
8
1
7
8
5
6
r
w
w
r
w
r
r
w
r
13 Communication options
13.1 The Supercal 5 can be fitted with up to two different optional
13.2 At the latest 6 seconds after the installation, the calculator unit
13.3 When connecting the communication modules, the installation
14 Display
The calculator Supercal 5 has the following display sequence:
• Main menu (Billing relevant data)
• Metrological
• Configuration
• Service
• Test Radio
15 LCD control concept
15.1 The control key can be used to select and confirm the various menus,
parameters, or other selection options within the display.
After 3 minutes the display of the calculator switches automatically
back to the main menu.
15.2 LCD (Standard-View)
4 wires sensor with
4 wires integrator
1/5 + 2/6 temperature high
3/7 + 4/8 temperature low
2
7
4
2
5
6
3
8
7
8
1
6
w
r
w
r
w
r
w
15.3 Commissioning Menu
w
r
w
r
w
16 Dimension Supercal 5
communication modules.
recognizes the plugged-in optional modules, and the functions are
freely available.
guidance - supplied with the unit - is to be considered.
The Right key has two functions:
• One single press and it selects next menu.
• Press it for Two Seconds in the "Overview Menu" and
you can enter to the highlighted menu.
• Left key is designated to select previous menu.
• If you are in any of the menus and you press both key,
LEFT and RIGHT fortwo seconds, you get back to the
"Overview Menu".
7
4
3
8
r
w
r
w
143
5.5
159.6
163.6
175.1
Menu's name
M1: Module installed in slot 1
M2: Module installed in slot 2
Commissioning:
commissioning menu
Con guration via NFC
3.9
53.5
© Danfoss | 2023.12 | 3

Publicidad

loading