Attributes
LocalTemperature
OccupiedCoolingSetpoint
EN
OccupiedHeatingSetpoint
ControlSequenceOfOperation
SystemMode
ACLouverPosition
Setpoint Raise/Lower
12
THERMOSTAT CLUSTER
Read (R) / Write (W)
LocalTemperature = 100 x temperature
R / W
Specifies the cooling mode setpoint
R / W
when the room is occupieed.
Specifies the heating mode setpoint
R / W
when the room is occupieed.
Specifies the possible system modes
that the thermostat can operate in.
R / W
Supported values are:
Specifies the current operating mode
of the thermostat.
Supported values are:
R / W
Specifies the current position of the
louver on the AC.
Supported values are:
R / W
Commands received
To change Setpoint Mode and Value through 2 parameters:
* Mode:
- 0x00 = Heat (Adjust heat setpoint)
- 0x01 = Cool (Adjust cool setpoint)
Amount: Specifies the increase / decrease of the setpoint in
steps of 0.1 ºC
Values
in Celsius
- 0x00 = Cooling only
- 0x02 = Heating only
- 0x00 = OFF
- 0x01 = Auto
- 0x03 = Cool
- 0x04 = Heat
- 0x07 = Fan Only
- 0x08 = Dry
- 0x01 = Fully closed
- 0x02 = Fully open
- 0x03 = 1/4 open
- 0x04 = 1/2 open
- 0x05 = 3/4 open

Publicidad