10.1
980 - DA TI TECNICI - TECHNICAL DA T A - DONNEES TECHNIQUES - DA TOS TÉCNICOS
- DANE TECHNICZNE - TECHNISCHE DA TEN - MŰSZAKI ADATOK
I diametri degli ugelli sono espressi in 1/100mm – The diameter of the nozzles are indicated in 1/100mm -
Le diamètres des gicleur sont exprimés en 1/100mm - Diameter der Düsen ist in 1/100mm angegeben –
Los diámetros de las boquillas se indican en 1/100mm - A fúvókák átmérője 1/100mm-ben van kifejezve
- RDA:Regolazione dell' aria primaria; Regulation of primari air; Réglage del'air primaire; Primärluftein-
stellung; Regulación de la entrada del aire; Primer levegő szabályozás
- 5,5kW: Bruc.piccolo; Small burner; Petit bruleur; Kleinen brenners; Quemador pequeno; Kis égőfej
7 kW : Bruc.medio; Medium burner; Bruleur moyen; Mittleren brenners; Quemador mediano;
11 kW: Bruc.grande; Large burner; Bruleur grand; Große brenners; Quemador grande;
7 kW**: Bruc. Forno; Oven burner; Bruleur four; Backofen-brennerduesen; Quemador horno; Égőfej Sütő
10 kW: Bruciatore forno maxi; Bruleur four maxi; Backofen-brennerdüsen maxi; Quemador horno maxi; Sütő
maxi égőfej
12 kW: Bruc. Tuttapiastra; Solid top Burner; Bruleur de plaques coupe -feu; Gluehplatten-brennerdue-
sen; Quemador plancha; Égőfej Teli főzőlap
AT
Austria
AL
Albania
BE
Belgium
BG
Bulgaria
CH
Switzerland
CY
Cyprus
CZ
Czech Republic
DE
Germany
DK
Denmark
IT, IE, GR, GB, ES, PT, BG, CZ, DK, FI, EE, SE, HR, LT, LU, LV, NO, PL, RO, SI, SK, TR, AL, MK
Modelli – Models – Modèles – Modelle – Modelo – Modellek
Tipo – Type – Bauart – Típus
Potenza nominale - Nominal thermal power
- Puissance thermique nominale - Nominal
- Wärmeleistung - Potencia tèrmica nominal -
Névleges teljesítmény
Consumo gas - Gasconsumption -
Consommation de gaz - Gasverbrauch -
Consumo de gas - Gázfogyasztás
Bruciatore principale - Main burner - Brûleur prin-
cipal - Hauptbrenner - Quemador principal - Főégő
R.D.A.-X mm
BY PASS-Ø-1/100mm
Bruciatore pilota - Pilot burner - Brûleur pilote -
Leitflamme - Quemador piloto - Őrláng (max 0,25 kW)
Bruciatore principale - Main burner - Brûleur
principal - Hauptbrenner - Quemador principal
- Főégő
R.D.A.-X mm
BY PASS-Ø-1/100mm
Bruciatore pilota - Pilot burner - Brûleur pilote
- Leitflamme - Quemador piloto - Őrláng (max
0,25 kW)
*Pressione gas alla rampa / Inlet gas pressure
**7 kW: Bruc. Forno; Oven burner; Bruleur four; Backofen-brennerduesen; Quemador horno
THE PRESENT MANUAL IS PROPERTY OF THE MANUFACTURER. ANY REPRODUCTION, EVEN PARTIAL, IS PROHIBITED.
IL PRESENTE MANUALE È DI PROPRIETÀ DEL FABBRICANTE E OGNI RIPRODUZIONE ANCHE PARZIALE È VIETATA.
EE
Estonia
ES
Spain
FI
Finland
FR
France
GB
United Kingdom
GR
Greece
HR
Croatia
HU
Hungary
IE
Ireland
5,5 kW
(kW)
G30/31)
G20
m
/h
3
0,473/
G30/31
kg/h
G20 20 mbar*
165/250K
G20 20 mbar*
G30/31
28-30/37 mbar*
G30/G31
30/30 mbar*
G31 37 mbar*
G30/31
28-30/37 mbar*
G30/G31
30/30 mbar*
G31 37 mbar*
- K -
IS
Iceland
IT
Italy
LT
Lithuania
LV
Latvia
LU
Luxembourg
MK
Macedonia
MT
Malta
NL
Netherland
NO
Norway
7,0
11,0
kW
kW
A1
A1
A1
5,5
11
7
(6 kW
(6 kW
(8,6 kW
G30/31)
G30/31)
0,582
0,740
1,163
0,473/
0,678/
0,466
0,466
0,668
195L
245L
80
85
110
35
35
35
120K
120K
145K
75
75
85
21
21
21
K
K
PL
Poland
PT
Portugal
RO
Romania
SE
Sweden
SI
Slovenia
SK
Slovakia
TR
Turkey
7**
10
12
kW
kW
kW
A1
A1
A1
7
10
12
0,740
1,057
1,269
0,552/
0,788/
0,985/
0,543
0,776
0,971
200K
235K
270L
15
15
3
95
105
180
36
36
36
135K
155K
175K
10
8
7
65
80
115
19
19
19