1.4. DEVELOPMENT AND MANUFACTURE
2. DESIGN
2.1. MATERIAL
2.2. ACCESSORIES
3. MODE OF OPERATION
3.1. FUNCTION
CAUTION:
Installation may only take place in a non-ex-zone!
The extraction air is cleaned to 99.999 % of hydrocarbons by the integrated activated carbon filter so
that it can be directly given o to the ambient air. The extraction air flow containing pollutants does
not come into contact with energised components. Hence the appliance is suitable for suctioning out
cabinets defined in EN 14470 Part 1 rsp. DIN 12925 Part 1. There is thus no need for an extraction air
line leading to a safe place outdoors.
A CE conformity attestation (also in acc. with EC directive 94/9/EC - ATEX directive) is on hand.
Development/manufacture: asecos GmbH Sicherheit und Umweltschutz, D-63584 Gründau
SN: The type plate with the serial number is situated on the outside of the housing of the UFA.20.30.
RAL
7035
RAL
7016
Activated carbon filter (3,500 g) incl. suspended solids preliminary filter.
a
INFO:
The housing consists of high
grade sheet steel (St 1203),
t=1.25 mm, and is powder-
coated
a
frash air
c
b
activated carbon filter
b
c
ventilator
d
gases and vapours in cabinet
CAUTION:
Filter can only retain solvent vapours
d
(hydrocarbons). Please consult us if
other materials are to be stored.
Safe and faultless function is shown
by the ventilation and filter monitoring
mechanism which is fitted as standard.
(3.2)
EN
3
3