ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information
pack upon completion of work.
These instructions do not cover all variations in
systems nor provide for every possible contingency to
be met in connection with installation. All phases of
this installation must comply with NATIONAL, STATE
AND LOCAL CODES. Should further information be
desired or should particular problems arise which are not
covered sufficiently for the purchaser's purposes, the matter
should be referred to your installing dealer or local distributor.
A. GENERAL
The following instructions cover 2TTA0030,040,050 & 060AD
Condensing Units.
NOTE:
These outdoor units may be used with indoor units
equipped with Thermostatic Expansion Valve or Accutron™
Flow Control Check Valve (F.C.C.V.) assembly for refrigerant
flow control only.
Check for transportation damage after unit is uncrated.
Report promptly, to the carrier, any damage found to the unit.
To determine the electrical power requirements of the unit,
refer to the nameplate of the unit. The electrical power
available must agree with that listed on the nameplate.
B. LOCATION & PREPARATION OF THE
UNIT
1. When removing unit from the pallet, notice the tabs on
the basepan. Remove tabs by cutting with a sharp tool as
shown in Figure 2 (see page 2).
2. The unit should be set on a level support pad at least as
large as the unit base pan, such as a concrete slab. If this
is not the application used please refer to application
bulletin SSC-APG002-EN.
3. The support pad must NOT be in direct contact with
any structure. Unit must be positioned a minimum of
12" from any wall or surrounding shrubbery to insure
adequate airflow. Clearance must be provided in front
of control box (access panels) & any other side requir-
ing service access to meet National Electrical Code.
Also, the unit location must be far enough away from
any structure to prevent excess roof run-off water from
pouring directly on the unit. Do not locate unit(s) close
to bedroom(s).
4. The top discharge area must be unrestricted for at least
five (5) feet above the unit.
All manuals and user guides at all-guidesbox.com
Installer's Guide
Condensing Units
2TTA0030,040,050 & 060AD000A
1
5. When the outdoor unit is mounted on a roof, be sure the
roof will support the unit's weight. Properly selected
isolation is recommended to prevent sound or vibration
transmission to the building structure.
6. The maximum length of refrigerant lines from outdoor to
indoor unit should NOT exceed sixty (60) feet.
7. If outdoor unit is mounted above the air handler,
maximum lift should not exceed sixty (60) feet (suction
line). If air handler is mounted above condensing
unit, maximum lift should not exceed sixty (60) feet
(liquid line).
NOTE:
Refer to "Refrigerant Piping Software" Pub. No. 32-3312-02.
8. Locate and install indoor coil or air handler in accor-
dance with instruction included with that unit.
18-AC51D5-5
5 FT. ABOVE UNIT-UNRESTRICTED

Publicidad

loading

Resumen de contenidos para Trane 2TTA0030AD000A

  • Página 1 All manuals and user guides at all-guidesbox.com 18-AC51D5-5 Installer’s Guide Condensing Units 2TTA0030,040,050 & 060AD000A ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
  • Página 2 3. Determine the best starting point for routing the refriger- ant tubing — INSIDE OR OUTSIDE THE STRUCTURE. AS SHIPPED 4. Provide a pull-thru hole of sufficient size to allow both FIELD SUPPLIED liquid and gas lines. LIQUID LINE 18-AC51D5-5 © 2009 Trane...
  • Página 3 All manuals and user guides at all-guidesbox.com Installer’s Guide LIQUID LINE SERVICE VALVE GAS LINE SERVICE VALVE 5. Do NOT allow uninsulated liquid line to come in direct 3. Attach center hose of manifold gauges to vacuum pump. contact with bare gas line. 4.
  • Página 4 All manuals and user guides at all-guidesbox.com Installer’s Guide rolled edge (approximately five [5] turns) observing 6. Provide flexible electrical conduit whenever vibration WARNING statement on page 2. See Figure 4. transmission may create a noise problem within the structure. 10.
  • Página 5 All manuals and user guides at all-guidesbox.com Installer’s Guide TYPICAL FIELD HOOK-UP DIAGRAMS FOR 2TTA0030-060AD PRINTED FROM B152901 P02 NOTE NOTE PRINTED FROM B152903 P02 W2 present only on 2 stage thermostat and furnace PRINTED FROM B152907 P04 W2 present only on 2 stage thermostat and furnace Notes: LEGEND...
  • Página 6 All manuals and user guides at all-guidesbox.com Installer’s Guide 2TTA030,040,050 & 060AD OUTLINE DRAWING Note: All dimensions are in MM (Inches). MODELS BASE FIG. 2TTA0030AD 730 (28-3/4) 724 (28-1/2) 651(25-5/8) 3/8 137 (5-3/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4) 457 (18) 2TTA0040AD 730 (28-3/4) 724 (28-1/2) 651(25-5/8) 1-1/8 3/8 137 (5-3/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4) 457 (18) 2TTA0050AD...
  • Página 7 All manuals and user guides at all-guidesbox.com Installer’s Guide MOUNTING HOLE LOCATION Note: All dimensions are in MM (Inches). NOTE: For model base size, see table on page 6. From Dwg. 21D152989 Rev. 0 18-AC51D5-5...
  • Página 8 2 Check only necessary if heating unit is used for indoor section and wiring has been disturbed during installation of cooling equipment. 3 When applicable. 12/09 Trane www.trane.com Trane has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.
  • Página 9 All manuals and user guides at all-guidesbox.com Instrucciones de Instalación Unidad Condensadora 50 Hz 2TTA0030,040,050 & 060AD000A 18-AC51D5-5-ES...
  • Página 10 All manuals and user guides at all-guidesbox.com © 2009 Trane...
  • Página 11 All manuals and user guides at all-guidesbox.com C o n t e n i d o Información General ................4 Instalación de Líneas de Refrigerante ..........5 Evacuación del Sistema ..……............7 Conexiones Eléctricas ................ 8 Diagramas de Cableado en Campo ..........10 Dibujo Esquemático ................
  • Página 12 Se recomienda un aisla- en forma suficiente para los “Trane APB2001-02”. miento adecuado para eivtar que propósitos del comprador, deberá el sonido o las vibraciones sean referirse el asunto a su instalador o 3.
  • Página 13 All manuals and user guides at all-guidesbox.com Instalación de Líneas de Refrigerante C- VALVULA DE CONTROL El extremo interior de los juegos de 4. Provéa un orificio de tamaño líneas refrigerantes recomendadas suficiente que permita el paso de DE FLUJO “ACCUTRON” puede ser recto o con un doblez de ambas líneas de líquido y de gas.
  • Página 14 All manuals and user guides at all-guidesbox.com Instalación de Líneas de Refrigerante E - OPERACION DE LA EXTREMO INTERIOR TIPO SOLDABLE VALVULA DE SERVICIO OPERACION DE LA VALVULA DE SERVICIO DE LATON DE LAS LINEAS DE LIQUIDO Y GAS Las Válvulas de Servicio de latón tanto de líquido como de gas, se embarcan de fábrica en posición asentada para conservar la carga de...
  • Página 15 All manuals and user guides at all-guidesbox.com Evacuación del Sistema REVISION DE FUGAS 1. Al concluir la revisión de fugas, NOTA: Puede evitarse el evacúe las líneas de refrigerante y intercambio innecesario de el serpentín interior, antes de abrir IMPORTANTE: mangueras y lograr la completa Coloque las válvulas de las tuberías para...
  • Página 16 All manuals and user guides at all-guidesbox.com Conexiones Eléctricas 3. Una la manguera central del 9. Ahora ya puede abrirse la válvula Si las líneas de refrigerante son más múltiple con manómetros, a la de cierre en la tubería de líquidos. largas a los 15 pies y/o de diferente bomba de vacío.
  • Página 17 All manuals and user guides at all-guidesbox.com Conexiones Eléctricas 3. La fuente de energía debe H. PROCEDIMIENTOS I. PROTECTOR CONTRA corresponder a las especificaciones OPERACIONALES Y DE AMBIENTE MARINO de la placa de identificación de la REVISION unidad. En el caso de aplicaciones de unidades instaladas a una milla de Las fases finales de esta instalación 4.
  • Página 18 All manuals and user guides at all-guidesbox.com Diagramas de Cableado en Campo 18AC51D5-5-ES...
  • Página 19 All manuals and user guides at all-guidesbox.com...
  • Página 20 All manuals and user guides at all-guidesbox.com Datos Dimensionales 18AC51D5-5-ES...
  • Página 21 All manuals and user guides at all-guidesbox.com Procedimientos de Verificación Después de completar la instalación, se recomienda revisar todo el sistema siguiendo la siguiente lista: 1. Línea de refrigerante; revisión de fugas....................( ) 2. Líneas de succión y conexiones perfectamente aislados ..............( ) 3.
  • Página 22 Trane www.trane.com En virtud de que Trane mantiene una política de contínuo mejoramiento de sus productos y datos técnicos, se reserva el derecho de cambiar sus diseños y especificaciones sin previo aviso. La instalación y labores de servicio al equipo referido en esta publicación, deberá realizarse únicamente...
  • Página 23 All manuals and user guides at all-guidesbox.com...
  • Página 24 Date / Fecha December 2009 / Diciembre, 2009 Trane has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice. En virtud de que Trane mantiene una política de contínuo mejoramiento de sus productos Trane y datos técnicos, se reserva el derecho de cambiar sus diseños y especificaciones sin previo aviso.

Este manual también es adecuado para:

2tta0040ad000a2tta0050ad000a2tta0060ad000a