INSTALLATION INSTRUCTIONS
C-CP-D-SQ-(S3L, S6L, S9L)-SCCT Series
MOUNTING USING 3/4" PLUG IN THE BACK
1.
Remove the four screws attaching the lens diffuser to the housing
and set the screws and lens aside.
2.
Unscrew the (4) screws attaching the LED mounting plate/reflector
to the housing. See Figure 1. Pry open the LED mounting plate/
reflector using a screwdriver in the opening slots on the sides of
the LED mounting plate/reflector. See Figure 2.
3.
Disconnect the two halves of the quick disconnect connector
attaching the driver to the LED mounting plate/reflector. Set LED
mounting plate/reflector aside for later use.
4.
Remove ¾" plug in back wall of fixture for wiring access.
5.
Route the incoming power leads through the hole located in the
back of the housing.
6.
Fixture is best mounted by drilling through (4) drill points locations
in corners of the housing. See Figure 3. Secure housing to
mounting surface using customer supplied hardware appropriate
for mounting surface.
NOTE: For wet locations, high grade caulking material, such
as silicone rubber, should be used between back gasket and
mounting surface and at all screw locations to ensure a watertight
enclosure.
NOTE: Fixture can also be pendant mounted by threading the
customer supplied pendant into the ¾" mounting hole on the
top of the housing. If using center conduit hole for pendant the
wireway opening in the end of the pendant MUST be filled with a
high grade of silicone caulk supplied by customer to prevent water
from entering fixture through the pendant. In addition, Teflon tape
should be used on conduit threads.
7.
Complete the wiring to the incoming power per the Electrical
Connections section.
8.
Select the desired CCT and wattage using the switches on the
back wall of the housing. See Figure 4.
NOTE: Factory setting is 100% wattage and 4000K.
9.
Reconnect the two halves of the quick disconnect connector that
were disconnected in STEP 3.
IMPORTANT: Do NOT allow the LED mounting plate/reflector
to hang from the wires connecting the plate to the driver after
connecting.
10. Position LED mounting plate/reflector on housing and secure by
retightening the (4) screws in the corners.
NOTE: Make sure no wires are pinched when attaching plate.
11. Remove the protective cover over the LEDs and discard. See
Figure 5.
NOTE: Do NOT touch the LEDs or the wiring coming from the
circuit board during the installation process.
12. Replace the lens diffuser on housing and tighten the screws in
the (4) corners. Gradually tighten lens screws in an "X" pattern to
prevent lens damage.
NOTE: Do not overtighten lens screws to prevent damage to lens.
http://lighting.cree.com/warranty
Document:
LPN00473X0001A3_A
Created By:
TMT
ELECTRICAL CONNECTIONS
Fixture is equipped with universal volt driver 120-277V
(ie. 120V, 208V, 240V or 277V)
PHASE TO NEUTRAL WIRING 120/277V
1. Connect supply ground to fixture ground (green) lead.
2. Connect supply common to fixture neutral (white) lead.
3. Connect supply Vin to fixture hot (black) lead.
Tuck all wires carefully into wiring chamber ensuring that no wires
are pinched.
PHASE TO PHASE WIRING 208/240V
1. Connect supply ground to fixture ground (green) lead.
2. Connect supply L1 (Hot) to fixture neutral (white) lead.
3. Connect supply L2 (Hot) to fixture hot (black) lead.
Tuck all wires carefully into wiring chamber ensuring that no wires
are pinched.
FCC NOTICE
CAUTION: Changes or modifications not expressly approved could
void your authority to use this equipment.
This device complies with part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area
is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
CAN ICES-005 (A)/NMB-005 (A)
|
1-800-236-6800
Date:
5-20-2023

Publicidad

loading

Productos relacionados para C-LITE C-CP-D-SQ-S3L-SCCT Serie

Este manual también es adecuado para:

C-cp-d-sq-s6l-scct serieC-cp-d-sq-s9l-scct serie