OPERATING INSTRUCTIONS
PF/PFQ
MELTRIC Corporation / 4765 W Oakwood Park Drive Franklin, WI 53132
Tel. : 800 433 7642 / Fax : 414 433 2701 / e-mail : mail@meltric.com
A manufacturer of products using Marechal technology
meltric.com
INSTRUCCIONES
MODE D'EMPLOI
GENERAL
PF and PFQ Series plugs and receptacles are engineered for use in high
amperage applications where routine plug insertion and high reliability are required.
To ensure proper installation and use of the product, please follow all of the
instructions carefully.
WARNING
serious injury or death. These instructions must be followed to ensure the safe and
DANGER
proper installation, operation and maintenance of the MELTRIC
installation, disconnect all sources of power to the circuit to eliminate the risk of
CAUTION
electrical shock. In order to prevent disconnection under load, electrical
interlocking is required.
NOTICE
RATINGS
ADVERTENCIA
PF and PFQ Series plugs and receptacles are UL and CSA listed according to
DANGER
UL 1682 and CSA C22.2 No.182.1 These listings only apply for 300A and 400A
devices at 600V or less. 600A devices are not UL or CSA listed. WARNING! All
CAUTION
PF and PFQ devices are provided with manually operated auxiliary contacts that
must be wired to the coil of a contactor or similar switching device to prevent
accidental connection or interruption of live main power contacts. See schematic
AVISO
for safety circuit example. The ratings for auxiliary contacts are shown in Table 1.
Device
PFQ300
PF series
* Rating is not UL or CSA listed.
INSTALLATION
PF and PFQ devices should be installed by qualified electricians in
accordance with all applicable local and national electrical codes.
Before starting verify that the power is off, that the product ratings are appropriate
for the application, and that the conductors meet NEC code requirements. Tools
WARNING
required for installation include 7/ 8" (22mm) wrench or socket, 5/16" (8mm) allen
wrench and 10 mm wrench for PFQ only.
DANGER
CAUTION
Device
NOTICE
PFQ - 300A
PF - 300A
PF - 400A
PF - 600A
Recommended Torques:
Main Contacts: 30 ft-lb. (40 N-m)
Aux /Pilot Contacts: 15 in-lb (1.80 N-m).
General Notes & Precautions
1.
To prevent short circuiting the heat shrink sleeves provided must be used
over lugs and terminals after wiring.
WARNING
DANGER
2. The PF and PFQ inlets and receptacles and handles are symmetrical and thus
they can be mounted in any of four positions provided that the locking cam on
CAUTION
the receptacle remains easily accessible.
NOTICE
ADVERTENCIA
3. Lugs are not included with devices unless ordered.
DANGER
CAUTION
WIRING INSTRUCTIONS
AVISO
The cable sheath should extend at least 2 in. into handle or junction box.
For Plug or Connector with Angled Handle or Receptacle on Box
or Inlet on Box
• Use straight type compression lugs with 9/16" or 5/8" hole.
• Run the neutral & ground wires above the phases.
• Apply heat shrink over lugs at terminals.
For Plug or Connector with Straight Handle
• Use 90° lugs with 9/16" or 5/8" hole. Arrange the 90° lugs to minimize the
possibility of lugs touching
• Run the neutral & ground wires above the phases.
• Apply heat shrink over lugs at terminals.
NOTICE: Lugs crimped on the conductors must be bolted on the terminals with
the supplied M14 screws and washers. In order not to transmit this torque to the
molding, contact bodies should be held with a suitable wrench when tightening the
M14 screw.
The phase contacts are lower to allow the passage of the ground and neutral
above the phases.
ASSEMBLY
Angled Handle to Inlet or Receptacle Assembly
1. Attach inlet or receptacle to handle body then open cover on handle.
2. Connect the conductors to the terminals as described previously in 'wiring
instructions.'
3. Attach handle cover using a 8mm allen tool and 6 screws supplied.
4. Compress grease coated cable gland by tightening hub.
NOTICE: The recommended torque to achieve IP 67 is 150 to 280 ft-lb
(200-400 N-m), depending on cable jacket material and diameter.
5. Then tighten the cable clamps.
Junction Box to Inlet or Receptacle Assembly
1. Attach junction box to conduit. Attach cover to junction box using bolts provided.
2. Connect conductors to terminals as described previously in 'wiring instructions.'
3. Mount receptacle or inlet to junction box cover using bolts provided.
Auxiliary /Pilot Contacts
In order to prevent disconnection under load electrical interlocking is required.
Failure to do so could result in death or serious injury.
WARNING
A
DANGER
TO
B
LOAD
C
CAUTION
JUMPER 2 PILOT
NOTICE
CONTACTS TO
COMPLETE CIRCUIT
NOTE:
ROTATE RECEPTACLE LOCKING
CAM TO ENGAGE PILOTS
Typical PF/PFQ Control Circuit
PF: The four pilot /auxiliary terminals are numbered 1 to 4 and color coded.
Conductors must be stripped by 0.5 in (12 mm) and fully inserted into their respective
spring-assisted, tunnel type terminals. Tighten terminal screws until hand tight with
a 4 mm flat screwdriver. Recommended torque is 13 in-lb (1.5 N-m). Terminals will
accept flexible conductors up to 10 AWG (6 mm
PFQ: Eight pilot /auxiliary contacts are prewired and identified. Pilots are marked
P1 and P2, whereas auxiliary contacts are numbered 3 to 8. Conductors provided
have a cross-section of 14 AWG (1.5 mm
Mechanical Locking: PF Series
The cam has two positions:
Position 1: Unlocked, auxiliary/pilot contacts opened.
Position 2: Locked, auxiliary /pilot contacts closed. The plug is live and cannot be
removed.
Mechanical Locking: PFQ Series
The cam on the receptacle has three positions:
Position 1: Unlocked, auxiliary and pilot contacts opened. The cover or plug can
be removed.
Position 2: Locked, pilot contacts opened. The cover or plug cannot be removed
but pilot contacts remain open.
Position 3: Locked, auxiliary and pilot contacts closed. The plug is live and can
not be removed.
Position 1
Cam can be locked out in any of the three positions.
OPERATION
To ensure safe and reliable operation MELTRIC
used in accordance with their assigned ratings.
They can only be used in conjunction with mating receptacles or plugs manufactured
by MELTRIC
or another licensed producer of products bearing the
®
WARNING
gy trademark.
DANGER
MELTRIC
plugs and receptacles are designed with different keying arrangements,
®
so that only plugs and receptacles with compatible contact configurations and elec-
CAUTION
trical ratings will mate with each other.
Connection
NOTICE
1. Insert the plug into the receptacle. This unlocks the safety shutter on the
receptacle and allows it to rotate.
2. Rotate plug approximately 30° clockwise to engage the phase contacts and to
make the unit watertight. Turn the cam /mechanical lock to secure the receptacle
and engage the pilot contacts which energize the circuit.
Disconnection
1. Turn the cam/mechanical lock to disengage the pilot contacts and
de-energize the circuit.
2. Twist plug 30° counterclockwise to disengage the phase contacts.
Withdraw plug.
ACHIEVING RATED WATERTIGHTNESS
NOTICE: Proper steps must be taken to maintain water tightness at NPT fittings on
the plug handles or at the junction box. The use of a sealer tape is recommended.
IP 66 /67 rated ingress protection applies to the device when the plug and
receptacle are fully mated. When not in use the plug/inlet or connector/receptacle
can be kept watertight by utilizing the protective cap. Caps are fully engaged when
inserted into receptacle /inlet, rotated 30° clockwise and secured in place with the
locking cam.
Using the correct bushing and compression washer size is important.
The bushing must have as close a size as possible to the outer cable diameter.
The portion of the cable that passes through the bushing must be as circular as
possible to maintain ingress protection.
MAINTENANCE
WARNING
eliminate the risk of electrical shock.
DANGER
MELTRIC products require little ongoing maintenance. However it is good practice
CAUTION
to periodically perform the following general inspections:
NOTICE
• Check the mounting screws for tightness.
ADVERTENCIA
• Verify the weight of the cable is supported by the strain relief mechanism and
not by the terminal connections.
DANGER
• Check the IP gaskets for wear and resiliency. Replace as required.
CAUTION
• Verify the electrical continuity of the ground circuit.
AVISO
• Check the contact surfaces for cleanliness.
Deposits of dust or similar foreign materials can be rubbed off the contacts with
a clean cloth. Sprays should not be used, as they tend to collect dirt. If any
significant pitting of the contacts or other serious damage is observed they should
be replaced.
MANUFACTURER'S RESPONSIBILITY
MELTRIC's responsibility is strictly limited to the repair or replacement of any
product that does not conform to the warranty specified in the purchase contract.
MELTRIC
shall not be liable for any penalties or consequential damages
®
associated with the loss of production, work, profit or any financial loss incurred by
the customer.
MELTRIC
Corporation shall not be held liable when its products are used in
®
conjunction with products not bearing the
MELTRIC
products in conjunction with mating devices that are not marked with the
®
technology trademark shall void all warranties on
the product.
MELTRIC Corporation is an ISO 9001 certified company. Its products are
designed, manufactured and rated in accordance with applicable UL, CSA and IEC
standards. MELTRIC
Marechal keying standards established to ensure intermatablility with similarly rated
products manufactured by Marechal Electric Group.
There are inherent dangers associated with electrical
products. Failure to follow safety precautions can result in
Table 1 - Auxiliary Contact Ratings
120VAC 240VAC 480VAC 600VAC
7A
10A*
Table 2 - Wiring Terminal Capacity
Main Contacts
Minimum
2
AWG
2
AWG
2
AWG
2
AWG
PF/PFQ
PF/PFQ
RECEPTACLE/
INLET/PLUG
CONNECTOR
MALE PILOT
FEMALE PILOT
CONTACTS
CONTACTS
Position 2
1
2
1
2
Before inspecting, repairing, or maintaining MELTRIC
products, disconnect electrical power to the receptacle to
designs and manufactures its products in accordance with
®
5A
2A*
10A*
10A*
Maximum
600
MCM
600
MCM
600
MCM
600
MCM
PHASE
A
B
C
PILOT CIRCUIT
).
2
).
2
Postion 3
plugs and receptacles must be
®
technology trademark. The use of
INSPF_PFQ H
devices. Before
®
2A*
10A*
Aux. Contacts
Maximum
10
AWG
10
AWG
10
AWG
10
AWG
LINE
CONTACTOR
OR
BREAKER WITH
UNDER VOLTAGE
TRIP
COIL
PILOT CIRCUIT
POWER
SWITCH ETC.
technolo-
®
Back to Top
p
INSPF_PFQ H

Publicidad

loading

Resumen de contenidos para Marechal Electric Meltric PF Serie

  • Página 1 UL, CSA and IEC standards. MELTRIC designs and manufactures its products in accordance with ® Marechal keying standards established to ensure intermatablility with similarly rated products manufactured by Marechal Electric Group. Back to Top INSPF_PFQ H...
  • Página 2 ESPAÑOL INSTRUCCIONES DE OPERACIÓN PF/PFQ INSPF_PFQ H MELTRIC Corporation / 4765 W Oakwood Park Drive Franklin, WI 53132 Tel. : 800 433 7642 / Fax : 414 433 2701 / e-mail : mail@meltric.com Fabricante de productos que utilizan tecnología Marechal meltric.com.mx INSTRUCTIONS MODE D’EMPLOI...
  • Página 3 UL, CSA et IEC applicables. MELTRIC ® conceptions et fabrique ses produits à Marechal clavetage les normes établies pour assurer intermateability avec des produits ayant une note similaire fabriqués par Marechal Electric Group. Back to Top INSPF_PFQ G...

Este manual también es adecuado para:

Meltric pfq serieMeltric pfq-300aMeltric pf-300aMeltric pf-400aMeltric pf-600a