Descargar Imprimir esta página

PPA TRIFLEX FULL RANGE DISPLAY Manual Tecnico página 11

Tarjeta electrónica

Publicidad

Idiomas disponibles

Idiomas disponibles

Adjust the opening and closing speed of the gate.
Closing speed
Note: the adjustment is from 60Hz to 200Hz.
Speed close to the gate stop part during the opening.
Opening End of Travel Speed
The adjustment is from 10Hz (minimum) to 50Hz
(maximum).
Speed close to the gate stop part during the closing.
Closing End of Travel Speed
The adjustment is from 10Hz (minimum) to 50Hz
(maximum)
Speed to recognize the travel or the first movement
after the board being powered.
Recognition time speed
The adjustment is from 10Hz (minimum) to 50Hz
(maximum).
Adjust the permitted maximum strength, it is from
Operator strength
20 to 100%.
If necessary, it is possible to decrease the motor force
during the travel recognition, for example, to avoid
that the rack bar breaks.
End of travel strength and
It is also possible to increase the strength, if nec-
recognition 0% to 32%
essary, in smaller operators to guarantee the total
opening and closing.
It is recommended around 10% to operators in con-
dominiums and around 20% in residentials.
Selects the time the "LG" output is activated after the
gate is closed. The adjustment step is thirty seconds
(30s), with values from zero (0) to two hundred and
forty seconds (240s). This output is automatically ac-
tivated when any key of the DIP switch is triggered, or
Courtesy light time
the recognition process is started.
NOTE: This function can also be set to traffic light and
pre-flashing light for opening. However, only through
PROG or bult-in display these ends shall be set.
In some facilities, such as a condominium, it is neces-
sary that the gate closes automatically as soon as the
vehicle gets out from the gate path. In order to do
so, it must be installed a photocell and the "photocell
Photocell "follower mode"
follower mode" function must be enabled.
Press the (+) to enable it and to include the time
before the automatic closing. The minimum value
is zero (0) and the maximum value is eighty (80)
seconds.
20
It allows stopping the operator during the opening.
Off: the operator will always totally open. This mode
is frequently used in condominiums to avoid lots of
commands which come from different dwellers that
enable and stop the gate. Therefore, the gate will al-
Stop in the opening
ways totally open.
On: The operator can stop opening through a com-
mand.
Delay only: The operator shall stop if it is in the Delay
mode for the opening.
This function enables the pulse for a lock when the
gate is closing. During the closing movement and
Lock pulse in the closing
close to the physical stop limit the lock pin contracts
to ease the closing of the gate.
The minimum value of 20Hz with the increase of 1Hz
Start speed of the gate
up to 100Hz.
If necessary, the space between the stop and the
gate can be adjusted when the operator completes
the closing or opening cycle. It can be closer or far
from the stop. The minimum value of 0, increment
Gap between the gate and
and decrement from 1 to the maximum value of 16.
the stop
Note: To test the changes, it is necessary to operate
the gate once, so that the operator system performs
an opening and closing cycle.
Available Options:
-Residential: smaller-sized gates and low-power
Operator model
operators;
-Condominium: larger-sized gates and high-power
and high flow rated operators;
Warning: Solely change this function if it is sure
Operator output voltage
about the operator voltage. In case of doubt, let it in
60hz
127V. the standard value is 127V, which corresponds
the most part of operators (three black wires).
This function allows the configuration if the photocell
runs with normally open or close contact or resistive
mode.
-Normally open: The standby terminal is disconnect-
ed from the GND, it accepts a command, when it is
connected to the GND.
Configuring the photocell
-Normally close: The standby terminal shall be con-
contact
nected to the GND, it accepts a command when it is
connected to the GND.
-Resistive: The terminal shall have all the photocell
connected and then press the button (+) to set this
value as standard, any other different value which is
in will activate a photocell command.
21

Publicidad

loading