To configure the DIP switch:
DIP SW
1
2
3
* default
NOTE:
Configuring the DIP switches should be performed without the batteries connected.
1.
[For one-way operating mode]: Set the DIP switch 1 to 1-way, and configure either smoke (2),
heat (3) or smoke and heat.
NOTE:
Changing the DIP switch Smoke (2) to off will cause that Smoke Detector will not comply to EN14604.
2. [For two-way operating mode]: Set the DIP switch 1 to 2-way, and configure activation of the
Smoke and Heat detectors from the system panel. (In this mode, the DIP switch 2 & 3 settings are
irrelevant.)
3. Set the alarm system to registration mode.
a. Go to the main menu and select [9]>[1]>[1] (Programming > Devices > Zones)
b. Select a zone and press '√'
4. Open the battery compartment cover (see Figure 8).
WARNING:
The detector batteries are supplied inside of the unit, which are covered with
plastic wrapping. Remove the plastic wrapping from the batteries before
installation, and then perform a functional test of the detector according to the
Testing section of these instructions.
5. Remove the battery from the insulation material and reinsert it into the transmitter, paying
attention to the polarity.
6. Close the compartment cover.The detector will send a transmission. If the transmission is
successfully received by the system it will play a confirmation sound. If no confirmation sound is
heard send another transmission by pressing and releasing the tamper switch of the device.
7. After the detector is successfully registered the display shows: Save? Press √ to confirm and
continue entering other parameters for the chosen device.
10
Description
1-Way/2-Way selection
Smoke selection
Heat selection
1 & 2-Way Smoke & Heat Detector
Table 1
ON
2-Way*
Smoke Enabled*
Heat Enabled
OFF
1-Way
Smoke Disabled
Heat Disabled*