Output specification
Voltage
13.4 – 14.2 V DC (13.8 V DC nominal) on
mains power
10.0 – 12.3 V DC on battery standby
Max load current
See Model specification table above
Ripple
150 mV pk-pk max.
Load output Fuse
See Model specification table above
Overload
Electronic shutdown until overload or short
circuit removed (under mains power only)
Standby battery
Battery type
12 V DC Valve Regulated Lead Acid
Battery capacity
See below under Mechanical specifications.
Local Indicators
MAINS LED (Green)
Mains present
FAULT LED (Red)
Fault present: Output fuse fail or battery fuse
fail (requires load and battery to be
connected) † battery disconnected, loss of
mains, output short circuit or low output
voltage
Signaling Outputs
Tamper
N/C volt-free contact (See Table for rating).
Note: Contact closed when the lid is closed
† and unit securely mounted (TAMPER
INACTIVE condition).
GEN Fault (general)
† 0.1 A @ 60 VDC N/O volt-free contact.
Open when battery disconnected, output
fuse fail, battery fuse fail, output short circuit
or low output voltage.
EPS Fault (mains)
† 0.1 A @ 60 VDC N/O volt-free contact.
Open when loss of mains for more than
10 s.
Mechanical
Model
PM841, PM842
Enclosure dimensions
230 x 200 x 80
w x h x d (mm) [external]
Battery capacity
(7.2 Ah)
Weight (kg) excluding
2.0
battery
Environmental
Temperature
−10 to +40°C (operating) 95% RH non-
condensing
−20 to +80°C (storage)
Connections
+LOAD
+ve voltage O/P to load equipment
-LOAD
−ve voltage O/P to load equipment
EPS Fault
† Volt-free contacts for loss of mains
indication
† Volt-free contacts for general faults (see
GEN Fault
signaling outputs)
+BATT
Red lead to standby battery
-BATT
Black lead to standby battery
Tamper x 2
Tamper volt-free contact
Specifications subject to change without notice.
PM844-A
355 x 330 x 80
1 x BS127N
1 x BS131N
(18 Ah)
4.3
Regulatory information
Manufacturer
Carrier Fire & Security Americas Corporation, Inc.
13995 Pasteur Blvd, Palm Beach Gardens, FL
33418, USA
EU authorized manufacturing representative:
Carrier Fire & Security B.V., Kelvinstraat 7,
6003 DH Weert, The Netherlands
Year of
The last two digits of the date of manufacture
manufacture
(located on the product rating label) are the year
of manufacture.
Certification
European Union
2014/35/EU (Low Voltage directive): Hereby,
directives
Carrier Fire & Security declares that this device is
in compliance with the essential requirements
and other relevant provisions of Directive
2014/35/EU.
2014/30/EU (EMC directive): Hereby, Carrier
Fire & Security declares that this device is in
compliance with the essential requirements and
other relevant provisions of Directive 2014/30/EU
2011/65/EU (RoHs2 directive): Hereby, Carrier
Fire & Security declares that this device is in
compliance with the essential requirements and
other relevant provisions of Directive 2011/65/EU
2012/19/EU (WEEE directive): Products marked
with this symbol cannot be disposed of as
unsorted municipal waste in the European Union.
For proper recycling, return this product to your
local supplier upon the purchase of equivalent
new equipment, or dispose of it at designated
collection points. For more information see:
www.recyclethis.info.
2013/56/EU (battery directive): This product may
contain a battery that cannot be disposed of as
unsorted municipal waste in the European Union.
See the product documentation for specific
battery information. The battery is marked with
this symbol, which may include lettering to
indicate cadmium (Cd), lead (Pb), or mercury
(Hg). For proper recycling, return the battery to
your supplier or to a designated collection point.
For more information see: www.recyclethis.info.