Installation
Safety Information
To ensure proper operation:
Installation
This fixture has been designed and 3rd party tested to meet ANSI/ISEA Z358.1. The system must be tested periodically to be
sure it is functioning properly to meet the standard. Please refer to the ANSI/ISEA Z358.1 standard on testing requirements.
The installation, maintenance and location of all eyewash and eye/face washes must comply with the requirements of ANSI/ISEA
Z358.1. Workers who may come in contact with potentially hazardous materials should be trained regarding the location and
proper operation of emergency equipment per ANSI/ISEA Z358.1.
ANSI/ISEA Z358.1 requires this unit to be used with a clean, potable, uninterrupted supply of tepid water. Bradley plumbed
emergency fixtures require a minimum of 30 psi flowing pressure in order to function as designed and meet the ANSI/ISEA
Z358.1 standard.
Before installation make sure that this equipment will meet the requirements of the potential hazardous contaminants in your
location.
Installation of this system must be completed by a qualified plumber in compliance with all national and local codes. Compliance
and conformity to drain requirements and other local codes and ordinances is the responsibility of the installer.
Weekly Inspections
To ensure all eyewash and eye/face wash fixtures are ready to be used when needed, regular checks and maintenance must be
conducted. Weekly inspections must be conducted on all safety equipment to make sure a suitable flushing fluid supply is present
and to make sure the equipment is in good operating condition.
Water Temperature
ANSI/ISEA Z358.1 requires tepid water. Suitable range is 60°F to 100°F (16°C to 38°C). Personal injury is possible outside this
temperature range.
Supplies Required
• Pipe sealant
• Piping to 1/2" NPT water supply inlet on unit
• Sign-mounting hardware
• Backflow prevention device as required by UPC, IPC and/or local plumbing codes
Local codes may require the installation of a backflow prevention valve to complete proper installation. Backflow prevention
valves are not included with the fixture and may be supplied by the contractor or purchased from Bradley Corporation.
Bradley • 215-1933 Rev. A: ECO 21-05-033
S19-244 & S19-244FW
1/7/2022
3