LIGHTGRID CONTROLLER
there is a risk of premature failure of the luminaire.
Design connection cables for the control inputs of
DALI control gear (1-10 V, DALI etc.) to be 230 V mains
voltage-proof (basic insulation).
Control units
• Do not exceed the maximum permissible
ambient temperature ta of the control unit.
Exceeding this limit reduces the service life, and in
extreme cases there is a risk of premature failure
of the control unit.
• Lay out the connection cables for the control inputs
of DALI control gear 230 V mains voltage-proof
(basic insulation).
• A maximum of 32 DALI loads per DALI bus are
permitted.
Intended use
Intended for indoor use with a maximum ambient
temperature of: ta 50 °C
Safety class: II
Protection rating: IP20
Directive 2014/53/EU
Simplified EU Declaration of Conformity according
to the RED Directive if the luminaire is equipped
with a control gear unit with NFC interface or a radio
component:
TRILUX hereby declares that the following radio sys-
tem type complies with Directive 2014/53/EU:
...
LIVELINK
The full text of the EU Declaration of Conformity is
available on the Internet at:
www.trilux.com/eu-conformity
Disposal of waste electrical and electronic equipment
Always collect and dispose of old electrical
and electronic equipment separately at the
end of its service life. In case of doubt, seek
information about environmentally-compliant waste
disposal from your local district authority or special
waste disposal companies. Current information on the
energy efficiency class of the selected product version
can be found in the corresponding data sheet for the
luminaire. Instructions for replacing or removing the
light source in accordance with Regulation 2019/2020/
EU can be found at:
www.trilux.com/EcoDesign
6 | 32
10262844 | 221017 | © trilux.com
LIGHTGRID CONTROLLER
Product description
This module is a control unit for mixed white lighting
systems with bidirectional control. It offers connec-
tion options for 32 DALI loads (control gear units)
and for two external push-buttons and up to three
sensors.
TECHNICAL DATA
Input voltage
Input current (nominal)
Input frequency
Battery
DALI current
DALI devices
(stand-alone operation)
DALI cable length
Ambient temperature ta
Typ. TC point (max.)
Humidity
Push-button input
L cable length
Connection method
Service life
Standards
© trilux.com | 221017 |10262844
220-240 VAC
50 mA
50/60 Hz
Lithium button cell
CR1632 3V
64 mA
max. 32
max. 300 m
-10 ... +50°C
+65°C
1% to 90% r.h.
non-condensing
220-240 VAC
max. 50 m
Plug-in terminal
0.5-1.5mm²
rigid/flexible
>50.000 h
EN 55015,
EN 61547,
EN 41347-1,
EN 41347-11,
EN 55032,