4. TECHNICAL FEATURES
EN
Installation height
Detection angle
Power source
Consumption
Light output (L')
Ventilation output
(D1-D2)
Settings
Protection index (IP)
Class of electrical
insulation
Connection capacity
Usage conditions
Appearance
When switched on:
• The LED comes on for 40 seconds and then switches off (it comes on if a pre-
sence is detected).
• L output = 230V for 60 sec and then 0V (230V if a presence is detected).
• D1-D2 output = closed contact for 60 sec and then open contact (closed contact
if a presence is detected).
16
CPTA-S
(attached to the
ceiling)
Single phase 230 V 50/60 Hz
8 VA
230 V closed contact, switching power = 10A AC1
Fluorescent tube 3AX (cosΦ = 0.3); 1000W max. (Incandescent/
halogen) - 400VA parallel-compensated (42μF)
Dry contact closure, breaking capacity = 5A AC1 / 1A AC3
low 250 VAC or 30 VDC. Detached from brightness
Illumination output = brightness threshold adjustable from 10 to
2000 lux; adjustable delay time 5 sec / 5 min / 10 min / 20 min.
Ventilation output = adjustable delay time 10 sec / 10 min /
15 min / 30 min / 60 min
40
0 – 45°C; max. 90% RH without condensation
CPTA-E
(embedded into a false ceiling)
2.5 - 3.5 m
360°
12 VA
40 (power box = IP20)
2
0,75 - 1,5 mm²
White plastic casing