EN
Before installation, please read and follow these instructions. Incorrect installation may lead to serious injury.
Disconnect all power cables to be installed! Take precautions against unintentional switching on! The product
must be installed, maintained and dismounted by a skilled person according to the relevant regulation. An all-
pole mains switch shall be incorporated in the electrical installation of the building to provide simultaneous sep-
aration of at least 3 mm for all phases from the supply.
Somfy cannot accept any liability for defects and damage caused by failure to follow these instructions. Please
keep these instructions for future reference.
SOMFY hereby declares that this product is in compliance with the essential requirements and other relevant
provisions of the European Directives applicable to the European Union. A declaration of conformity is available
at www.somfy.com/ce.
www.somfy.co.uk
A
MOUNTING
[1] Choose the optimum location: flat and large sur-
face.
[2] Mount the Motor Controller
[3] Use cable tie!
[4] Keep to minimum distance!
B
WIRING
[1] Wiring diagram
[2] Tool for all terminals
[3] Check the correct running direction of the end
products
UP: All end products move upward
STOP: All end products stop
DOWN: All end products move downwards
[4] Possible switches
1. Smoove Origin IB, ref. 1811272
2. Double push button unlocked
C
CONFIGURATION
[1] Reset/Prog button
With this button, you can access the basic configura-
tion of the motor controller.
1. Green LED
Blinks, when no RTS module exists
2. Yellow LED = Screen Mode
3. Orange LED = Venetian blind EU mode
4. Red LED = Venetian blind US mode
LED flashes = no running time existing
LED glows = running time stored
[2] Selection of motor, electronic or standard
Preset motor type is Electronic Motor (ELM)
Somfy TLW25 WT. Switching to standard
motor (STM) Somfy LV/LW25 is possible.
1. Entering the programming mode.
2. To toggle between modes, press shortly the
Reset/Prog button. Repeat until desired LED
lights up.
3. Save and exit.
Using a prohibited functional mode can
damage the motors! The mode is specified
for all 4 motor outputs!
[3] Selection of switch ergonomics
The different ergonomics are described in the
manual:
• Screen ergonomics (SCR)
• Venetian blind with EU ergonomics
• Venetian blind with US ergonomics (default
mode)
1. Entering the programming mode.
2. To toggle between modes, press shortly the
Reset/Prog button. Repeat until desired LED
lights up.
3. Save and exit.
[4] Factory reset
[5] Learn running time/length
1. Move screen to upper end limit
2. Press Stop until screen moves down on its own
3. Press Stop when lower end limit is reached
D
SYMBOLS
[1] Actions
1. Up
2. Down
3. Stop
[2] End product status
1. Up movement
2. Down movement
3. Upper end limit
4. Lower end limit
animeo Motor Controller 4DC KNX WM AC Ref. 5172914A