CARLO GAVAZZI EM24 Instrucciones De Uso página 11

Analizador de energía trifásico

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 63
Settings from EM24 IS
General settings
The available settings depend on the application set.
Page title
Sub-menu
Cng PASS
-
APPLiCAt
User
USEr 1
USEr 2
USEr 3
SELECtor
SELEC. 1
SELEC. 2
SELEC. 3
SELEC.LoC
SYS
-
Ut rAtio
-
Ct rAtio
-
P int.ti
-
diG in 1
diG in 1
Prescal 1
diG in 2
diG in 2
Prescal 2
diG in 3
diG in 3
Prescal 3
FiLtEr.S
-
FiLtEr.Co
-
AddrESS
AddrESS
bAudrAtE
Ene t.rES
End
-
Note: the Ut rAtio is available for compatibility with other versions, even though the AV5 version is not meant to be used with voltage transformers. It should
be therefore set to 1.
Description
Change password
Application
User
Page displayed according to selector
position among the available pages for
each application (see "Frontal selector"
on page 15)
System
Voltage transformer ratio (VT)
Current transformer ratio (CT)
Dmd integration time (min)
Function
Pulse weight
Function
Pulse weight
Function
Pulse weight
Interval of filter intervention with respect
to full scale (%)
Filter coefficient
Serial address
Baud rate
Reset of all the total counters
Exit and save
Values
From 0 to 9999
tYP.A
tYP.b
tYP.C
tYP.d
tYP.E
tYP.F
tYP.G
tYP.H
From 1 to 9999
From 1 to 9999
From 1 to 9999
From 1 to 31
From 1 to 31
From 1 to 31
From 1 to 31
3P.n
3P.1
2P
1P
3P
Note: MID (PFA, PFB): only 3P.n
From 1 to 6000
From 1 to 60000
From 1 to 30
tAr, GAS, m3 Cold, m3 Hot, kWh tot, kWh out, rEM, SYnC
From 0.01 to 99.99
tAr, GAS, m3 Cold, m3 Hot, kWh tot, kWh out, rEM, SYnC
From 0.01 to 99.99
GAS, m3 Cold, m3 Hot, kWh tot, kWh out, rEM
From 0.01 to 99.99
From 0 to 100
From 1 to 32
From 1 to 247
4.800 or 9.600
YES/no
-
EM24 IS - Instruction manual | CARLO GAVAZZI Controls SpA
Configure the system
Default value
0
tYP.b
1
2
3
1
28
31
3
3P.n
1
1
15
SYnC
10
SYnC
10
-
10
2
2
1
9600
no
-
11

Publicidad

loading