INSTRUCTION MANUAL
SPECIFICATIONS
Model
Loudspeaker
Rated Power (RMS)
Power Taps 100 V
Impedance
Sensitivity SPL (1 W / 1 m)
Sound Pressure SPL (20 W / 1 m)
Freq. Range
Dispersion 1 kHz / 4 kHz
Operating temperature
Protection range
Dimension (mm)
Weight
Finish
Grille
Mounting
Connector
EN54 Standard
POWER SELECTION
A-225DEN_ESP_ENG_v1.0
WAGO 221 connector (Screwdriverless Installation)
Loudspeaker for voice alarm systems for fire detection and fire alarm systems for buildings
Impedance
100 V
-
COM
6 W
1667 Ω
3 W
3333 Ω
1.5 W
6667 Ω
1/1
CEILING SPEAKER
WARNING:
. Installation by qualified personnel only.
. Speakers must be wired in parallel and connected to
the correct line terminals of amplifier.
. Ensure that all speakers have the same polarity with
respect to each other.
Do not select another taping if the speaker is in use.
.
No naked flame sources, such as lighted candles,
.
should be placed on the apparatus
A-225EN
5"
6 W
6 W, 3 W & 1.5 W
1667 Ω, 3333 Ω & 6667 Ω
90 dB
98 dB
80 ~ 20,000 Hz
180º / 75º
-10ºC ~ +55ºC
IP-21C
Ø 180 x 93 (depth)
0.78 kg
Metal housing / RAL9016 colour
Metallic
Quick fit mounting
EN 54-24:2008
Ref. No.: DOP_A225DEN
ID-Code: A225DEN
1438/CPR/0981
Ceiling Loudspeaker, 6W, Type A
CE-Symbol according 93/68EWG
Color
Black
Red
White
Green
A-225DEN
.