Descargar Imprimir esta página

Klaxon Nexus 120dB Instrucciones De Instalación

Publicidad

Enlaces rápidos

EN
DE
FR
Tone
Tone Type
1.
970Hz (BS5839-1:2002)
2.
800Hz/970Hz @ 2Hz (BS5839-1:2002)
3.
800Hz – 970Hz @ 1Hz (BS5839-1:2002)
4.
970Hz 1s OFF/1s ON (Apollo Fire Systems Alert Tone, BS5839-1:2002)
5.
970Hz, 0.5s/ 630Hz, 0.5s (Apollo Fire Systems Evacuate Tone, BS5839-1:2002)
6.
554Hz, 0.1s/ 440Hz, 0.4s (France – AFNOR NF S 32 001 )
7.
500 – 1200Hz, 3.5s/ 0.5s OFF (Netherlands – NEN 2575:2000) Dutch Slow Whoop
8.
420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone)
9.
500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (Australia AS1670 Evacuation tone)
10.
550Hz/440Hz @ 0.5Hz
11.
970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 Low tone)
12.
2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201 High tone)
13.
1200Hz – 500Hz @ 1Hz (DIN 33 404)
14.
400Hz
15.
550Hz, 0.7s/1000Hz, 0.33s
16.
1500Hz – 2700Hz @ 3Hz (Vandal Alarm)
17.
Simulated Bell
18.
840Hz
19.
660Hz
20.
660Hz 1.8s ON/1.8s OFF
21.
660Hz 0.15s ON/0.15s OFF
22.
510Hz, 0.25s/ 610Hz, 0.25s
23.
800/1000Hz 0.5s each (1Hz)
24.
250Hz – 1200Hz @ 12Hz
25.
500Hz – 1200Hz @ 0.33Hz.
26.
2400Hz – 2900Hz @ 9Hz
27.
2400Hz – 2900Hz @ 3Hz
28.
800Hz – 970Hz @ 100Hz
29.
800Hz – 970Hz @ 9Hz
30.
800Hz – 970Hz @ 3Hz
31.
800Hz, 0.25s ON/1s OFF
32.
500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220)
33.
340Hz
34.
1000Hz
35.
1400Hz – 1600Hz, 1s/1600Hz – 1400Hz, 0.5s (NF 48-265)
36.
660Hz 6.5s ON/13s OFF
37.
1000Hz/2000Hz, 1s each
38.
720Hz, 0.7s ON/0.3s OFF
39.
970Hz, 0.25s ON/OFF
40.
2800Hz, 1s ON/OFF
41.
2800Hz 0.25s ON/OFF
42.
2400/2900 @ 2Hz
43.
Chime, 554Hz/440Hz Single shot 'ding dong'
44.
Chime, 554Hz/440Hz Repeating 'ding dong'
45.
Chime, 970Hz/800Hz Single shot 'ding dong'
46.
Chime, 970Hz/800Hz Repeating 'ding dong'
47.
Hooter, Repeating
48.
Gentle alarm - Tone 2, rises slowly to full volume over 30s
49.
Time-Out Alarm – As Tone 2, cuts off after 10 mins
50.
Time-Out Alarm – As Tone 2, cuts off after 2 mins
51.
750Hz 0.33s ON/0.51s OFF
52.
750Hz 0.51s ON/0.33s OFF
53.
550Hz, 0.33s/1000Hz, 0.7s
54.
600Hz – 900Hz/ 0.9s
55.
660Hz – 680Hz/ 0.9s
56.
670Hz – 725Hz/ 0.9s
57.
920Hz – 750Hz/ 0.9s
58.
700Hz - 900Hz, 0.3s/0.6s OFF
59.
900Hz - 760Hz, 0.6s/0.3s OFF
60.
750Hz
61.
Power Only – Use with Stage 3 control for manual/intermittent chime triggering
62.
Power Only – Use with Stage 3 control for manual/intermittent chime triggering
63.
Power Only – Use with Stage 3 control for manual/intermittent horn triggering
64.
Reserved for future use
www.acornfiresecurity.com
Installation Instructions
ES
NL
Tone Description / Application
www.acornfiresecurity.com
Nexus 120 AC Sounder & Sounder-Beacon
PT
IT
Dip Switch
(S1/S2)
O-O-O-O-O-O
O-O-O-O-O-I
O-O-O-O-I-O
O - O- O - O- I - I
O-O-O-I-O-O
O- O - O- I - O- I
O- O - O- I - I- O
O - O - O - I - I - I
O-O-I-O-O-O
O- O - I- O - O- I
O- O - I- O - I- O
O - O - I - O - I - I
O- O - I- I - O- O
O - O - I - I - O - I
O - O - I - I - I - O
O - O - I - I - I - I
O-I-O-O-O-O
O- I - O- O - O- I
O- I - O- O - I- O
O - I - O - O - I - I
O- I - O- I - O- O
O - I - O - I - O - I
O - I - O - I - I - O
O - I - O - I - I - I
O- I - I- O - O- O
O - I - I - O - O - I
O - I - I - O - I - O
O - I - I - O - I - I
O - I - I - I - O - O
O - I - I - I - O - I
O - I - I - I - I - O
O - I - I - I - I - I
I-O-O-O-O-O
I- O - O- O - O- I
I- O - O- O - I- O
I - O - O - O - I - I
I- O - O- I - O- O
I - O - O - I - O - I
I - O - O - I - I - O
I - O - O - I - I - I
I- O - I- O - O- O
I - O - I - O - O - I
I - O - I - O - I - O
I - O - I - O - I - I
I- O - I - I - O - O
I - O - I - I - O - I
I - O - I - I - I - O
I - O - I - I - I - I
I- I - O- O - O- O
I - I - O - O - O - I
I - I - O - O - I - O
I - I - O - O - I - I
I - I - O - I - O - O
I - I - O - I - O - I
I - I - O - I - I - O
I - I - O - I - I - I
I - I - I - O - O - O
I - I - I - O - O - I
I - I - I - O - I - O
I - I - I - O - I - I
I - I - I - I - O - O
I - I - I - I - O - I
I - I - I - I - I - O
I - I - I - I - I - I
PL
SE
DK
3rd Stage
Peak Sound
Tone
Level (dBA@1m)
18
118
1
120
1
120
1
118
1
118
1
119
1
120
1
116
1
119
19
119
1
118
1
111
1
119
18
115
1
120
1
118
1
114
1
119
10
114
19
114
19
113
1
115
1
119
1
115
1
119
1
113
1
114
1
119
1
119
1
120
1
120
1
120
1
113
18
116
1
119
19
114
1
116
1
118
1
118
1
111
1
111
1
114
1
116
1
116
1
117
1
117
1
115
1
120
1
120
1
120
1
118
1
119
1
116
1
119
1
116
1
118
1
119
1
120
1
119
18
118
43
43
47

Publicidad

loading

Resumen de contenidos para Klaxon Nexus 120dB

  • Página 1 www.acornfiresecurity.com Nexus 120 AC Sounder & Sounder-Beacon Installation Instructions Tone Tone Type Tone Description / Application Dip Switch 3rd Stage Peak Sound (S1/S2) Tone Level (dBA@1m) 970Hz (BS5839-1:2002) O-O-O-O-O-O 800Hz/970Hz @ 2Hz (BS5839-1:2002) O-O-O-O-O-I 800Hz – 970Hz @ 1Hz (BS5839-1:2002) O-O-O-O-I-O 970Hz 1s OFF/1s ON (Apollo Fire Systems Alert Tone, BS5839-1:2002) O - O- O - O- I - I...
  • Página 2 110V Beacon (Where fitted) 230V IP Rating IP66 with suitable cable glands Synchronisation Automatic with Klaxon Nexus and b. Remote Tone Switching (If required): Externally link control terminals Sonos Sounders as shown below. *depends on selected tone. Alarm Stage Stage 1 Example Signal ‘Alert’...
  • Página 3 IP-Klasse IP66 Synchronisation Automatique avec les sondeurs Synchronisierung Automatisch mit Klaxon Nexus- Klaxon Nexus et Sonos und Sonos-Alarmgebern *variable selon la tonalité sélectionnée *je nach gewähltem Ton. La directive européenne " Déchets d'Equipements Electriques et Electroniques " (DEEE) a pour but de minimiser l'impact des déchets électriques et électron- Das Ziel der EG-Richtlinie über Elektro- und Elektronik-Altgeräte ist, Umwelt- und...
  • Página 4 www.acornfiresecurity.com Instrucciones de Instalación Montageinstructies Instalación Installatie a. La unidad debería ajustarse con un cilindro recto soplado que incorpora a. Het apparaat moet voorzien zijn van een aansluiting met aarding die un dispositivo de desconexión de todos los polos y proporciona una voorzien is van een ontkoppelingapparaat voor alle polen en met een separación de contacto de 3 mm en todos los polos.
  • Página 5 www.acornfiresecurity.com Manual de Instalação Istruzioni di installazione Instalação Installazione a. A unidade deve ser instalada com uma derivação com fusível incorporando a. L'unità deve essere installata con un supporto di sostegno con fusibili um dispositivo de desligamento de todos os pólos que proporciona contenente un dispositivo di disconnessione di tutti i poli che fornisce 3mm de separação entre os contactos de todos os pólos.
  • Página 6 www.acornfiresecurity.com Instrukcja montażu Installationsmanual Installation Instalacja a. Enheten ska förses med ett säkrat uttag med en frånslutningsanordning a. Urządzenie powinno posiadać zabezpieczony wyłącznik umo liwiający för alla poler som ger ett kontaktavstånd på 3 mm för polerna. odłączenie wszystkich biegunów tak, aby odległość między stykami Kontrollera att märkdata för säkring, kabelstorlek och packboxtyp är wynosiła 3 mm.
  • Página 7 www.acornfiresecurity.com Installationsanvisninge Installation a. Apparatet skal udstyres med en afgreningsledning med sikring og frakoblingsmulighed for alle poler, der skal give en kontaktafstand på 3 mm ved alle poler. Sørg for at mærkeeffekt for sikring, kabelstørrelse samt type pakdåse er tilstrækkelig til den samlede belastning på lydalarmens kredsløb.

Este manual también es adecuado para:

Nexus 120Pnc-0023Pnc-0009Pnc-0011Pnc-0056Pnc-0058