5.2.9 System filtration pilot function
Option 1; P3=0 Filtration pump is related to heat pump operation to start and stop.
Filtration pump starts 60s before compressor, filtration pump start 30s and then the water flow switch detect flow.
Before the heat pump enters into Standby mode, the compressor stops first and after 5 minutes filtration pump
stops.
Condition
P3=0,
Heating
T1≥Tset-0.5℃,
mode
last for 30
minutes
P3=0,
Cooling
T1≤Tset+0.5℃,
mode
last for 30
minutes
Option 2; P3=1 Filtration pump is always on, P2=0 the timer function is no active
Under condition P3=1, whenT1≥Tset+1℃(T1≥29℃) last for 3 minutes, heat pump will be in standby, while filtration
pump is always on.
Under option 2, with activation of the timer; P2=1 to start and stop the filtration pump according the
programming of the P4 (time), P5 (timer ON) and P6 (timer OFF)
Condition for the heat pump start, timer ON actives;
When the timer reaches the set time of TIMER ON, the filtration pump will start and after 5 minutes the heat
pump start. The heat pump stays in stop if the water in temperature is ≥ Tset+1℃, before the TIMER OFF, the
filtration is still activated.
Condition to stop the heat pump, timer OFF actives;
When the timer reaches the set time of the TIMER OFF, the heat pump will stop and after 5 minutes the filtration
pump stops.
If heat pump is turned ON/OFF manually, the filtration pump will start and stop accordingly.
NOTE :
Tset = Tseting water temperature
For example : Tset = 28℃ Tseting water temperature in your pool heat pump
Tset-0.5 = less 0.5℃ than Tseting temperature, Tset- 0.5 = 28-0.5=27.5℃
Tset+0.5= more 1℃ than Tseting temperature, Tset+ 0.5 = 28+0.5=28.5℃
Example
1. Then it enters into
standby mode for 1 hour
P3=0,
(It will not restart except
T1≥27.5℃, last
turn it on manually.)
for 30 minutes
1. Then it enters into
P3=0,
standby mode for 1 hour
T1≤28.5℃, last
(It will not restart except
for 30 minutes
turn it on manually.)
Water pump working logic
2. After 1 hour, the filtration pump
will restart for 5 minutes. If the
T1≤27℃, the heat pump will start
to work until T1≥27.5℃ and last for
30 minutes to go into standby
2. After 1 hour, the filtration pump
will restart for 5 minutes. If it tests
T1≥29℃, the heat pump will start
to work until T1≤28.5℃ and last for
30 minutes to go into standby
62