Instructions
rements-Parts 2: Design, construction, testing,
marking and documentation
Low Voltage Directive 2014/35/EU EN 60335-
1:2012 + A11:2014- Household and similar elec-
trical appliances-Safety-Part 1: General require-
ments-for all above mentioned condensing units
Eco-design DIRECTIVE 2009/125/ EC, esta-
blishing a framework for the setting of Eco-de-
sign requirements for energy-related products.
REGULATION (EU) 2015/1095, implementing Eco-
design Directive 2009/125/EC with regard to Eco-
design requirements for professional refrigerated
storage cabinets, blast cabinets, condensing
units and process Chiller.
• Condensing unit measurements are made
according to standard "EN 13771-2:2007" – Com-
17 - Fan speed controller setting for R134a/R513A refrigerant
Fan speed Controller
FSC type
Spare part number
061H3144
061H3248
XGE-2C
* Installer can set the required setting based on application.
18 - Dual Pressure switch factory settings
Refrigerants
R404A/R507/R407A/R407F/R448A/R449A/R452A
R134a/R513A
© Danfoss | Climate Solutions | 2022.02
pressor and condensing units for refrigeration-
performance testing and test methods- part 2:
Condensing units
15 - Warranty
Always transmit the model number and serial num-
ber with any claim filed regarding this product.
The product warranty may be void in following
cases:
• Absence of nameplate.
• External modifications; in particular, drilling,
welding, broken feet and shock marks.
• Compressor opened or returned unsealed.
• Rust, water or leak detection dye inside the
compressor.
Refrigerant
For Refrigerant
letter
G
R134a/R513A
Q
R404A/R452A/R507
H
R404A/R507
R404A/R507/R134a/R513A/ R407A/
X
R407F/R448A/R449A/R452A
Y
R404A/R507/R449A
B
R404A/R507/R448A/R449A/R452A
X
If refrigerant used is R134a or R513A
High pressure settings (bar (g))
ON
23
13
• Use of a refrigerant or lubricant not approved by
Danfoss.
• Any deviation from recommended instructions
pertaining to installation, application or mainte-
nance.
• Use in mobile applications.
• Use in explosive atmospheric environment.
• No model number or serial number transmitted
with the warranty claim.
16 – Disposal
Danfoss recommends that condensing
units and oil should be recycled by a sui-
table company at its site.
Factory
Action required*
setting
8 bar
15 bar
360°=1 turn = Approx 0.8 bar
(Clockwise rotation =
15 bar
Increase pressure setting,
Counter clockwise rotation =
15 bar
Decrease pressure setting)
15 bar
15 bar
Rotate the screw by 9 turns in counter
15 bar
clockwise direction to reach 8 bar
Low pressure settings (bar (g))
OFF
ON
27
2
17
2
118A0549G - AN23308644013405-001701 | 5
OFF
1
1