Information for the tester
Insulation Resistance (R ISO )
Measuring method:
Current-voltage measurement as per IEC 61557-2
Nominal voltage:
< 520 V DC
Open-circuit voltage:
approx. 520 V DC
Nominal current:
1 mA DC
Short-circuit current:
< 12 mA DC
Permissible overload:
max. U
= 600 V AC (measurement is not started)
rms
Electrical safety is given during and functional safety after overload.
Measuring Range
Resolution
0,01-0,05-9,99 MΩ
10 kΩ
0,1-0,5-99,9 MΩ
100 kΩ
k
Measuring time: while key
„Start" is pressed, but max. 25 s
followed by automatic discharge of device undertest
DC voltages Range
Resolution
1 520 V
1 V
Internal resistance:
approx. 470 kΩ (L/N-PE)
serves as discharge resistance for any capacitances in the measuring circuit
Max. noise voltage:
U
= 50 V AC, at higher voltages no measurement is
rms
started!
Internal Loop-Network Resistance (R LOOP )
Measuring method:
Lowering of voltage as per IEC 61557-3
Nominal voltage:
110/230/400 or. 127/220/380V sinusoidal
Functional range 101...152; 180...435 V
Frequency range:
46 - 65 Hz
Test current:
dependent on mains voltage and network impedance
(Load resistance < 80 Ω; I ~ 3 A at 230 V, 5,5 A at 400 V)
≤ 18°; cos phi ≥ 0.95
Network impedance angle:
Additional error
for cos phi: < 0.95:
±...% of m.v. = (1-cos phi) . 100
Intrinsic error
± (8 % of m.v. + 1 digit)
Intrinsic error
± (8 % of m.v. + 1 digits)
55