173 Amplification of
locking signal
174 Pump overrun time
175 Periodic pump run
(pump kick)
176 Winter- / summer-
time changeover
177 Summer- / winter-
time changeover
178 Clock operation
179 Bus power supply
180 Outside tempera-
ture source
181 Heat demand output
Ux DC 0...10 V
194 Hours run counter
195 Controller's soft-
ware version
Building Technologies
100 %
(0...200)
....................
6 min
(0...40)
min
................
0
(0 / 1)
.........................
25.03
(01.01. ... 31.12)
25.10
(01.01. ... 31.12)
0
(0...3)
.........................
A
(0 / A)
.........................
A
(A / 00.01...14.16)
.........................
130 °C
(30...130)
...................
Display function
Display function
74 319 0618 0 a
Response to locking signals
%
0 = no periodic pump run
1 = weekly pump run activated
Setting: Earliest possible change-
over date
Setting: Earliest possible change-
over date
0 = autonomous clock in the
controller
1 = clock from bus (slave), with no
remote setting
2 = clock from bus (slave), with
remote setting
3 = controller is the central clock
(master)
0 = no bus power supply through
the controller
A = bus power supply through the
controller
No display means: Controller is
autonomous (no data bus pre-
sent).
Setting when supplied via the data
bus: segment and device number
of source, or A for automatic
identification of source
Scaling for DC 10 V
°C
Number of controller operating
hours
17.04.2008
en