1 Presentation of the Conventional Fire Detection and Fire Alarm Control
Panel CLVR.
The conventional fire detection and fire alarm control panel CLVR from COFEM, represents all
the experience accumulated during the design and manufacture of control panels after more
than 40 years in the marketplace.
This control panel consists of different models so as to be more precisely adapted to the needs
of each installation, offering 4 models of control panels with different capabilities: CLVR02Z (2
Zones), CLVR04Z (4 zones), CLVR08Z (8 Zones) and CLVR12Z (12 Zones).
Technical characteristics:
Control panel up to 12 zones for use of conventional detectors and manual call points.
Up to 32 elements (with detectors and manual call points) per zone.
2 monitored general sounder output, delayable from 0 to 10 minutes, and protected by a
fuse.
1 immediate alarm output through a dry NO/NC contact (Normally Open/Normally Closed).
1 fault output through a dry NO/NC contact (Normally Open/Normally Closed), delayable
from 0 to 10 minutes (CLVR08Z and CLVR12Z models have NO/COM –Normally
Open/COMmon contacts).
Two 30V/DC monitored auxiliary outputs protected by a fuse for external power supply as
sounders, relay units, etc (CLVR02Z and CLVR04Z models have 1 output).
It has a test mode for quickly and easy checking of detectors and manual call points.
It allows configuration of the Open line, alarm detector and alarm manual call point
thresholds for adjusting to operation with other detectors.
The last detection zone can be configured as a monitoring input for an external fire
protection system indicating fault.
Metal box with front bolted door, 4 predrilled holes of 28 mm, and 1 rectangular of 140 x 40
mm for running wiring and space for two 7Ah batteries.
MODBUS protocol with RS485 on demand.
ON-LINE Software possibility using the MODBUS functionality.
CONTACTID on demand.
Certified according to standard EN 54-2, and EN 54-4.
Dimensions: 363 x 331 x 96 mm.
TECHNICAL SPECIFICATIONS
Supply voltage
Output voltage
Consumption in standby
Consumption in alarm
Batteries
Battery fuse
Battery charger
Elements per zone
Control Panel Power Supply
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - cofem@cofem.com - www.cofem.com
Conventional Fire Detection and Fire Alarm Control Panels
CLVR02Z
CLVR04Z / CLVR08Z / CLVR12Z
/
110~230V 50-60Hz/AC
Maximum current per zone
21V Nominal
End of line resistor
70 mA
Sounder output voltaje S1
140 mA
Sounder output voltaje S2
2 x 12V 7Ah SLA
Fault output
4 A
Environmental conditions
500 mA 27V/DC 20ºC
Measurements
32
Weight (without batteries)
3 A
Standards
Maximum current output 30V
1)
CLVR08Z and CLVR12Z have this designation / Value.
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
2 mA (on standby)
4 K7
1)
30Vdc 1 A / 1,85 A
1)
30Vdc 1 A / 0,75 A
Yes
-10ºC +50ºC 20%-95% HR
363 x 331 x 96 mm
4,3 Kg
EN 54-2, EN 54-4
1)
0,75 A / 1,5 A
27