Automatic Set-Up - ICAR 5LSA Instrucciones De Uso

Ocultar thumbs Ver también para 5LSA:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

grammed.
In this case during the system installation and once the controller is powered up, the dis-
play will view a flashing Ct (Current Transformer). The CT primary can be set directly by
pressing + and -.
Once programmed, press MANU/AUTO to confirm. The unit will store the setting and
directly restart in automatic mode.

1.11 AUTOMATIC SET-UP

The setting is useful if it is not possible to access the C.T. or else when the characteristics
The automatic set-up of parameters allows the unit to be placed in service without having
to program any parameter.
To activate the automatic set-up when the unit is in MANU or --- mode, simultaneously
press MODE and MANU/AUTO keys for 5 seconds.
The wording ASE (Automatic Set-up) flashes indicating that the automatic set-up of the
parameters is in progress.
The procedure will last a few minutes during which the controller measures the power
rating of the connected steps. This measurement will then be continuously updated during
the normal operation.
If the load of the system varies frequently, the same step may have to be measured sev-
eral times. In this case, the procedure may last longer.
At the end of the automatic set-up, the controller is ready for automatic operation.
It is recommended to avoid substantial current variations as much as possible during the
automatic set-up. During this automatic set-up, the controller is not able to monitor certain
data such as CT primary current, rated capacitor voltage.
Therefore we shall have as follows:
The current cannot be viewed in Amperes but only as a percentage.
The ∆kvar and Σkvar measurements are not available.
The measurement and protection for capacitor overload are not accessible.
All of the relays are considered as normal capacitors banks. So no alarm relay or fan
control configuration is possible.
The capacitors installed must be with a power rating which is a multiple of 1, 2, 4, 8 or
16 times the smallest capacitor step.
The unused steps must be placed at the higher step numbers.
Note: After termination of the automatic set-up, if access is gained in manual mode to
setting the parameters, the controller will consider all the parameters present as valid.
Therefore, all of the measurements and functions will be available once again.
Never use if a complete panel has been purchased.
of the capacitor banks are not known.
CAUTION!
IMPORTANT!
33