The compressor starts but the relay does not open
1
Electrical connections incorrect.
2
Low voltage at compressor.
3
Relay locked closed.
C
4
Excessive discharge pressure.
5
Electric motor – winding interrupted or in short
circuit.
Thermal circuit breaker intervention
1
Low voltage at compressor (three-phase motor –
phase imbalance).
2
Thermal circuit breaker faulty.
3
Faulty run capacitor.
4
Excessive discharge pressure.
D
5
High suction pressure.
6
Compressor overheated - hot return gas.
7
Electric motor – winding interrupted or in short
circuit.
The compressor starts and runs at brief operating
cycles
1
Thermal circuit breaker.
2
Thermostat.
3
High-pressure
insufficient condenser cooling.
E
4
High-pressure switch intervention due to excess
refrigerant gas charge.
5
Low-pressure
insufficient refrigerant gas charge.
6
Low-pressure
expansion valve restriction or blockage.
The compressor runs continuously or for long periods
1
Insufficient refrigerant gas charge.
2
Thermostat contacts blocked in the closed
position.
3
System insufficiently sized for the charge.
F
4
Excess charge to be cooled or insufficient
insulation.
5
Evaporator covered with ice.
6
System circuit restriction.
7
Condenser blocked.
Run capacitor damaged, interrupted or short circuited
1
Incorrect run capacitor
G
Starter relay faulty or burnt out
1
Incorrect relay.
2
Relay fitted in incorrect position.
H
3
Incorrect run capacitor
switch
intervention
switch
intervention
due
switch
intervention
due
1
Check the electric circuit.
2
Find and remove the cause.
3
Find and remove the cause.
4
Find the cause and replace the relay if
necessary.
5
Replace the compressor.
1
Find and remove the cause.
2
Check characteristics and replace if
necessary.
3
Find and remove the cause.
4
Check the ventilation and any restrictions
or obstructions in the system circuit.
5
Check the sizing of the system. Replace
the
condensing
powerful one if necessary.
6
Check the refrigerant charge; repair any
leaks and add gas if necessary.
7
Replace the compressor.
1
See the previous point (thermal circuit
breaker intervention).
2
Small differential: correct adjustment.
due
to
3
Check the correct operation of the fan
motor or clean the condenser.
4
Reduce the refrigerant charge.
to
5
Repair any leaks and add refrigerant gas
if necessary.
to
6
Replace the expansion valve.
1
Repair any leaks and add refrigerant gas.
2
Replace the thermostat.
3
Replace the system with a more powerful
one.
4
Reduce the charge or improve the
insulation, if possible.
5
Defrost.
6
Identify the cause and remove it.
7
Clean the condenser.
1
Replace with a capacitor of the correct
type.
1
Replace with a relay of the correct type.
2
Fit the relay in the correct position.
3
Replace with a capacitor of the correct
type.
BLOCKSYSTEM FA - FT Pag. 31
UK
unit
with
a
more
REV. 04 10/07