Remember that the range within which these parameters are set
is provided by the machine operating limits. The minimum and
USER SETTING
Water inlet temperature in Cold
Cold Setting
mode operation.
Water inlet temperature in Cold
Heating Setting
mode operation.
2nd C. Set
Second Cooling set.
2nd H. Set
SECOND HEATING SET.
INSTALLATOR SET
Proportional temperature band within which the compressors
Tot. diff.
are activated and deactivated
Set AG
Antifreeze Alarm temperature, EV side (water outlet temperature).
Low Pressure Alarm bypass time, after the compressor start-
Esc.B.P.
up.
Antifreeze setting for evaporator input gas temperature.
AG Evap
Can be overridden.
B.AG Evap
Evaporator antifreeze alarm bypass from On CP, end defrosting.
CP1 Power
% power of compressor 1 compared with the machine 100% value.
CP2 Power
% power of compressor 2 compared with the machine 100% value.
CP1A Power
% power of compressor 1A compared with the machine 100% value.
CP2A Power
% power of compressor 2A compared with the machine 100% value.
CP1B Power
% power of compressor 1B compared with the machine 100% value.
CP2B Power
% power of compressor 2B compared with the machine 100% value.
Compressor 1 operating hours.
CP 1 Time
This value can only be reset.
Compressor 2 operating hours.
CP 2 Time
This value can only be reset.
Number of worked hours for the 1A compressor.
OreCP1A
This value can only be reset.
Number of worked hours for the 2A compressor.
OreCP2A
This value can only be reset.
Compressor 1B operating hours.
OreCP1B
This value can only be reset.
Compressor 2B operating hours.
OreCP2B
This value can only be reset.
14
Description
WARNING
The settings listed in the following table can be visualised by the user,
but they can be only modified by the technical After Sales Service.
If these settings are modified by non-authorised personnel, the war-
ranty shall be considered void.
Description
8.

SETTING MENU

maximum values to be set only represent one characteristic of
regulation.
Min.
Default
Max.
-10 °C
7.0°C
20°C
30°C
50°C
50°C
-10 °C
11°C
20°C
30°C
45°C
50°C
SET
Water/Air Water/Water
4
4
j
4
4
4
j
4
Default value
5°C
3°C
3'
-8 °C
20 sec.
25%
25%
25%
25%
0
0
0
0
0
0
0
0