Set-Temperature Positive Blast Chilling And Storage Cycle
Prior to starting
•
the cycle:
To start the cycle:
•
•
•
•
During chilling:
•
•
•
•
•
•
10
CK640_ML_A5_v4_20200728.indb 10
CK640_ML_A5_v4_20200728.indb 10
the display shows the residual chilling time remaining
the LED
is on
parameter r2 sets the chilling time duration
parameter r8 sets the operational set point
press
several times to:
- display the message "nEg"
- display the cabinet temperature
- exit the procedure, or leave for 15 seconds
the device switches to storage mode
the display shows the message "End"
the buzzer sounds for the period of time set by parameter AA
press any key to mute the buzzer; press once more to cancel the message
"End"
the display shows the cabinet temperature
the LEDs
and
are on
the parameter rA sets the operational set point
press
several times to:
- display the message "nEg"
- exit the procedure, or leave for 15 seconds.
press
for 2 seconds
A test is run in order to check correct pin probe insertion
- if the outcome of the test is positive, the cycle will be started
- if the outcome of the test is negative, the cycle will be started in timed
mode.
ensure the device is in "stand-by" mode and no procedures are running
press
to select "PoS" and ensure the LED
press
or
within 15 seconds to change the value (the setting
remains active until another cycle is selected, when the value assigned by
parameter r3 is restored)
press
: after 2 minutes, the appliance will run set-temperature positive
blast chilling and storage cycle
the display shows the temperature measured by the pin probe
the LED
is on
the parameter r3 sets the blast chilling endpoint temperature
the parameter r5 sets the maximum chilling time duration
the parameter r7 sets the operational set point
press
several times to:
- display the maximum residual chilling time remaining
- display the message "PoS"
- display the flashing cabinet temperature
- exit the procedure, or leave for 15 seconds
is flashing