16
5. INTERNAL FITTINGS
Inserted shelves:
Installed as per the installation instructions (on the inside of the cabinet door).
Please comply with the maximum working load of the inserted shelves
(see Appendix)!
If the inserted shelves are installed other than in accordance with the installation
instructions, the maximum working load cannot be guaranteed.
Containment tray / perforated plate cover:
The containment tray in the base area of the safety cabinet has the function of cont‑
aining any liquids that leak within the cabinet. It is not an additional shelf for storage of
containers.
10 %
1
10 %
1
Use of storage shelves within cabinets with multiple storage levels:
Leakage:
ɽ Liquids in the containment tray must the wiped up using suitable media.
ɽ The choice of media is the responsibility of the operating company.
According to EN 14470‑1: A containment tray must be
installed underneath the lowest storage level. The cont‑
ainment tray must have a minimum containment volume
110 %
of 10 % of all the containers stored in the cabinet (Fig. 1),
2
or at least 110 % of the volume of the largest individual
container (Fig. 2), whichever volume is larger.
110 %
2
CAUTION:
Use as a storage shelf is permissible only if a
perforated plate is used.
1
www.hoffmann-group.com
2
3