5. Installing the R-Converter Unit (mm)
Parts to procure locally
•
Suspension bolts or anchor bolts : W3/8 (M10)
•
Nut : W3/8 (M10)
•
Washer : W3/8 (M10)
Installing the unit in a ceiling
(1) Install the suspension bolts.
(2) Install the R-Converter unit.
Installing the unit on a wall
(1) Install the anchor bolts.
(2) Install the R-Converter unit.
Do not install the refrigerant pipes on top of the unit
when installing the unit on a wall, otherwise
condensation can enter the electrical devices,
which can cause an electric shock or a fire.
6
Suspension bolt
Nuts
Washer (procure locally)
Unit
Washer (procure locally)
Nut (procure locally)
VIEW "A"
Anchor bolt pitch
Wooden structures
•
Use tie beams (single storied houses) or second floor beams (two
story houses) as reinforcing members.
•
Wooden beams for suspending air conditioners must be sturdy and
their sides must be at least 6 cm long if the beams are separated
by not more than 90 cm. The size of the suspension bolts should
be M10 (W3/8). (The bolts are not supplied with the unit.)
A Ceiling
B Rafter
C Beam
D Roof beam
B* Suspension bolt pitch
Ferro-concrete structures
Secure the suspension bolts using the method shown, or use steel or
wooden hangers, etc. to install the suspension bolts.
E Use inserts rated at 100-150 kg each (procure locally)
F Suspension bolts M10 (W3/8) (procure locally)
G Steel reinforcing rod
Ensure that this face is always installed
upwards.
Suspension bolt pitch
Suspension bolt
MIN. 200
Install the R-Converter
unit horizontally.
Obstructions
Anchor bolt
MIN. 500
SERVICE SPACE
MIN. 200
Wall
Washer
(procure locally)
Nuts
(procure locally)
MAX. 50