4. Dimensions and required servicing space of Branch Box
PAC-AK31BC (3-branches type)
450
205
C
B
A
C
B
A
25
25
25
21
75
75
Fig. 4-3
(1)
450
Min. 50
Min. 250
Fig. 4-4
Fig. 4-6
(3)
Min.250
Fig. 4-7
5. Refrigerant piping
* Always follow the specifications written in the installation manual of the outdoor unit. Exceeding these requirements may cause reduced performance of the
equipment, and malfunctions.
4
320
12
91
95
280
39
61
79
50 34
73
200
23
Type A
200
Type B
(2)
*1
Min.
Min.
250
280
250
180-200
B
*3
Fig. 4-5
450
PAC-AK31BC (Fig. 4-3)
(mm)
Suspension bolt: W3/8 (M10)
Refrigerant pipe flared connection
A
Liquid pipe
ø6.35
Gas pipe
ø9.5
Drain hose size: O.D.0 (VP16)
4.1. Space required for installation and servicing
(1) Front View (Fig. 4-4)
Branch box
A
On the side of piping
B
() Side View (Fig. 4-5, Fig. 4-6)
For indoor installations
C
Ceiling board
D
Maintenance hole
E
A
PCB side
F
*1: A minimum 350 mm is required for 90° bends in refrigerant piping.
*2:
is " Min. 200 mm " <recommendation>.
(Premise: The slope of drain piping is securable 1/100 or more. Required
200 mm or more, when not securable.)
In the case of less than 00 mm (for example
of Branch box from a maintenance hole becomes difficult (Only exchange work
of a PCB, linear expansion valve coils, sensors and drain pan is possible).
*3:
is "
600 mm " <recommendation>.
In the case of " 450", prepare a maintenance hole at a PCB side (as it is shown
in Fig. 4-6), and "Min. 300 mm" is needed as distance
In the case of less than 300 mm (for example
work of Branch box, linear expansion valve coils, sensors, and drain pan from a
maintenance hole becomes difficult (Only exchange work of a PCB is possible).
(3) Top View (Fig. 4-7)
Refrigerant piping
G
When facing in the opposite direction to the refrigerant piping.
H
B
C
ø6.35
ø6.35
ø9.5
ø9.5
is 100 mm), the exchange work
.
is 100 mm), the exchange
To outdoor unit
ø9.5
ø15.88