4. Dimensions and required servicing space of Branch Box
(mm)
(1)
B
50
450
250
Fig. 4-6
Fig. 4-8
(3)
G
Min. 250
Fig. 4-9
(mm)
Fig. 4-10
Fig. 4-12
5. Refrigerant piping
* Always follow the specifications written in the installation manual of the outdoor unit. Exceeding these requirements may cause reduced performance of the equipment,
and malfunctions.
6
(2)
C
A
*1
250
278
250
D
E
180-200
*3
Fig. 4-7
E
D
450
Fig. 4-11
NO
NO
YES
NO
(mm)
4.2. Space required for installation and servicing
1. The space when installing with the suspension bolts.
(1) Front View (Fig. 4-6)
A
Branch box
B
On the side of piping
() Side View (Fig. 4-7, Fig. 4-8)
*2
C
For indoor installations
D
Ceiling board
E
Maintenance hole
*1: Minimum 350 mm is required for 90° bends in refrigerant piping.
*2:
is "Min. 200 mm" <recommendation>.
(mm)
In the case of less than 00 mm (for example
of Branch box from a maintenance hole becomes difficult (Only exchange work
of a PCB, linear expansion valve coils and sensors are possible).
*3:
is "
600 mm" <recommendation>.
In the case of "
450 mm", prepare a maintenance hole at a PCB side (as it is
shown in Fig. 4-8), and "Min. 300 mm" is needed as distance
In the case of less than 300 mm (for example
of Branch box, linear expansion valve coils and sensors from a maintenance
(mm)
hole becomes difficult (Only exchange work of a PCB is possible).
(3) Top View (Fig. 4-9)
G
Refrigerant piping
2. The space when installing on the floor. (Fig. 4-10)
3. The space when installing on a wall. (Fig. 4-11)
The installation direction is limited when installing on a wall. (Fig. 4-1)
(mm)
When installing the unit on the wall, install the piping connected to the outdoor
unit facing down. Other ways are not acceptable.
is 100 mm), the exchange work
.
is 100 mm), the exchange work