8. TECHNICAL SPECIFICATION

Quattro
PowerControl / PowerAssist
Integrated Transfer switch
AC inputs (2x)
Maximum feed through current (A)
Minimum PowerAssist current (A)
INVERTER
Input voltage range (V DC)
Output
(1)
Cont. output power at 25 °C (VA)
Cont. output power at 25 °C (W)
Cont. output power at 40 °C (W)
Peak power (W)
Maximum efficiency (%)
Zero-load power (W)
Zero load power in AES mode (W)
Zero load power in Search mode (W)
CHARGER
Charge voltage 'absorption' (V DC)
Charge voltage 'float' (V DC)
Storage mode (V DC)
Charge current house battery (A)
Charge current starter battery (A)
Battery temperature sensor
GENERAL
Auxiliary AC output
Programmable relay
(5)
Protection
(2)
VE.Bus communication port
General purpose comm. port
Common Characteristics
ENCLOSURE
Common Characteristics
Battery-connection
120 V AC-connection
Weight (kg)
Dimensions (hxwxd in mm)
STANDARDS
Safety
Emission / Immunity
1) Can be adjusted to 50 Hz
2) Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. 120VAC on inverter output
g. Input voltage ripple too high
3) Non linear load, crest factor 3:1
4) At 25 °C ambient
5) Programmable relays which can be set for general alarm, DC undervoltage or genset start signal function
AC rating: 120V/4A
DC rating: 4A up to 35VDC, 1A up to 60VDC
12/5000/220-100/100
120V
Input voltage range: 90-140 VAC
9,5 – 17
Output voltage: 120 VAC ± 2%
5000
(3)
4500
4000
10000
90
25
20
6
14,4
13,8
13,2
220
(4)
4
For parallel and three phase operation, remote monitoring and system integration
Operating temp.: -20 to +50°C (fan assisted cooling)
Material & Colour: aluminium (blue RAL 5012)
24/5000/120-100/100
120V
Yes
Yes
Input frequency: 45 – 65 Hz
AC-in-1: 100A
AC-in-2: 100A
AC-in-1: 18A
AC-in-2: 18A
19 – 33
Frequency
5000
4500
4000
10000
91
25
20
6
28,8
27,6
26,4
120
4
yes
Max load: 50A Switches off when in inverter mode
Yes, 3x
a - g
Yes, 2x
Four M8 bolts (2 plus and 2 minus connections)
M6 bolts
101 lb
46 kg
18,3 x 13,7 x 11 inch 464 x 348 x 280 mm
EN 60335-1, EN 60335-2-29
EN55014-1, EN 55014-2, EN 61000-3-3
48/5000/70-100/100
120V
Power factor: 1
38 – 66
60 Hz ± 0,1%
:
5000
4500
4000
10000
92
25
20
6
57,6
55,2
52,8
70
Humidity (non condensing) : max 95%
Protection: IP 21
27