OPERATION INSTRUCTIONS

RECOVER AND RECYCLE REFRIGERANT FROM AN AC SYSTEM
1. Be sure that the shut off valves are off prior to attaching to a vehicle AC system.
2. Attach the machine to the high and low sides of the AC system to be serviced. The R-
134a hoses have SAE approved shut-off valves (quick disconnects). The hoses are
shut off when disconnected from the AC system and are open only when connected
with the knurled knobs turned clockwise. Slide the collar of the fitting back and press to
the appropriate fitting.
• Blue hose to the low side of AC system
• Red hose to the high side of AC system
3. Set MAIN POWER (k, Figure 3) ON.
4. Open the valves on the service hoses by turning the knurled knob clockwise (Figure
12). This will allow refrigerant to flow to the vehicle.
5. Observe the pressure readings on the low and high side manifold gauges. If the
readings are zero, then repair AC system leak or proceed to vacuum phase.
6. Open the High Side and Low Side valves on the control panel of the machine.
7. Press and hold the SEL key until the LED corresponding to "RECOVERY" lights; then
press GO. At this point the RECOVERY/RECYCLING phase will begin and the
"Recovery" LED will flash.
8. During the RECOVERY/RECYCLING phase the amount of refrigerant recovered from
the vehicle will be displayed. Upon completion of the recovery phase the machine will
stop and hold three minutes.
9. During this time the machine automatically discharges the used oil. It will be necessary
to monitor this oil dumping to determine the amount of oil that must be added to the
vehicle. When the oil discharge is complete, measure, record and empty the oil
discharge bottle. This amount will be added to the AC system before charging. When
there is no increase in system pressure, the vacuum pump will start and evacuate the
input oil separator inside the VR-6000.
10. If, during this 3-minute time period, the residual refrigerant left in the A/C system
causes the pressure to increase, the machine will automatically resume recovering the
refrigerant. When this phase is complete the machine will sound and audible alarm,
and switch to the REFRIGERANT AVAILABLE display.
11. Close the High Side and Low Side panel valves.
12. Set the MAIN POWER switch OFF.
13. Disconnect the machine if desired. (See DISCONNECTING THE MACHINE FROM A
VEHICLE.)
14. Make necessary repairs to the A/C system being serviced.
REMOVING NON-CONDENSABLE GASES
As non-condensable gases accumulate in the refrigerant storage tank, excessive pressure
is created. The most noticeable symptom of excess pressure is a slow down of refrigerant
flow during the recovery process. In most cases, you will not notice a reduction in refrigerant
recovery rate until the nominal pressure in the storage tank is 20 psig above the normal
pressure, as listed on the purge chart. Check for non-condensable gases after each
recovery phase. The table provided below (Figure 13) is used to determine when an excess
of non-condensable gases has accumulated in the refrigerant storage tank.
INSTRUCTIONS MANUAL
16