8 . B A T T E R Y
The battery is the only UPS component which is not in permanent use. It has a useful life of
approximately 3 to 5 years. However, frequent major discharges or exposure to temperatures
over 20 C will shorten its life span. We therefore recommend that users recharge the battery
once every 3 months when the unit is not in use in order to compensate for natural discharging.
UPS backup time will depend on the powered load, as well as the age and condition of the
batteries.
WARNING!
Batteries should always be replaced by qualified technicians. Batteries have a very high
short circuit current: connection errors could cause electric arcs resulting in serious
burns.
9 . T R O U B L E S H O O T I N G
Should the UPS fail to function correctly we recommend you perform the following tests before
calling the Hot Line.
PROBLEM
No LED display on
front panel.
In the event of power
failure, backup time is
shortened.
Mains normal but the
unit is on battery mode
(LED is flashing)
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 01 13 AA 59 208 15
POSSIBLE CAUSE
Low battery.
Faulty battery.
UPS is not turned on.
UPS overload.
Battery voltage is too low.
Battery defect due to high
temperature operating
environment, or improper
use of battery.
Fuse is broken.
Loose power cord.
SOLUTIONS
Charge battery for up to 8 hours.
Replace with the same type of battery.
Press the power switch again to turn
on the UPS.
Remove some non-critical load.
Charge battery up to 8 hours.
Replace with the same type of battery.
Replace Fuse
Connect the power cord properly.
7